Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit Messaging

Publication 2755-6.8

The following figure describes the format and mapping of
transaction blocks for request and response messages in the scanner
module.

service

port

TXID

command

size

MAC ID

Service Data

word 224

Transaction
Header
(3 words)

word 225

15

0

Class

Instance

Attribute (optional)

Transaction #1

Format of 32-word M0 Transfer File

for Explicit Message Request

service

port

TXID

status

size

MAC ID

Service Response Data

word 224

Transaction
Header
(3 words)

word 225

15

0

Transaction #1

Format of 32-word M1 Transfer File

for Explicit Message Response

Processor and Scanner Module Manage Messages

File transfer operations between the processor and the scanner
always originate in the processor. The scanner module can only wait
for the processor to download a transaction block to the module or
request an upload of a transaction block from the module.

Once an Explicit Message Request transaction block is downloaded
to the scanner module, a ladder logic program in the processor polls
the scanner module for the transaction block containing the Explicit
Message Response for that request. This is done by the processor
with an M1 file transfer on the scanner module. Depending on the
network load, the scanner could take a few seconds to complete the
request. When a response is loaded, bit 15 of the module status
register is set to 1. The program may have to poll the scanner
module a number of times before the scanner returns a Response
Transaction Block.

The scanner module recognizes I/O data and control as higher
priorities over explicit messaging on DeviceNet.