4–12

Downloading Match Codes via DH485 Protocol with an SLC 5/03

t

or SLC 5/04

t

Controller

Publication 2755-6.8

DH485 Master Mode

1. Click the Protocol Edit button in the Serial Port dialog.

2. Set the parameters as follows:

From the Master/Slave box, select Master

From the Destination Node box, select 1

This is the SLC node where the decoded bar codes are sent.

From the Maximum Node box, select 2

This is the number of nodes on the network.

From the N9:Offset box, select 100 which is the default

This is the SLC destination address where the decoded bar
codes are sent. N9: is reserved for communications. Bar code
data is sent as an ASCII string to the SLC N9 file.

From the Node box, select 2

This is the DH485 node address.

In this application the response in N9:100 will be 3F90 for a
successful match code download or 3F94 for a match code
download failure. (3F is the hexadecimal value of the
AdaptaScan device address 63. This will be different for a
different applied address.)

3. Click OK to return to the main Serial Port dialog.

4. Click Save and Close to return to the main Project dialog.