Communicating with a PLC-5 Processor on a DeviceNet Network using Explicit Messaging

Publication 2755-6.8

Notes on using Explicit Messaging

You can send messages sequentially from the PLC-5 to different
bar code readers, but the response will not update properly (when
the response is read in N25:0).

The TXID byte does not need to be incremented, although you
may not know where the response came from.

To receive the correct response from the command sent from the
PLC-5 you must:

1. Send command down, matchcode download (TXID=11).

2. Send a 03 in the status command. Refer to page 12–21 for

more information.

3. Increment TXID to 12.

4. Send command down, turn on LED 1 (TXID=12).

5. View N25:0 for response to step 4.

6. Confirm that TXID=12. If your response is 90, the command

was sent correctly. If you receive a 94, the command was not
sent correctly.

If an incorrectly formatted command is sent from the PLC-5, you
must send a 03 in the status command byte in order for the system
to operate properly.