Troubleshooting your module – Rockwell Automation 2755-SNx Adaptascan Bar Code Readers User Manual

Page 219

Advertising
background image

11–19

Communicating with a PLC-5 Processor on a DeviceNet Network

Publication 2755-6.8

The bicolor (green/red) module status indicator displays device
status. The LED indicates whether the device has power and is
functioning properly.

If the Module LED is

this indicates

Take this action

Off

there is no power applied to
the module.

Apply power.

Solid green

the module is operating in
normal condition.

None

Flashing green

the module is not configured.

Configure the module.

Flashing red

there is invalid configuration.

Check configuration setup
and verify dip switch settings.

Solid red

the module has an
unrecoverable fault.

Replace the module.

Channels 1 and 2 each have a bicolor (green/red) network status
indicator. The following table provides troubleshooting information
about the Channel 1 and 2 communication links.

If the NET indicator is

this indicates

Take this action

Off

the channel is disabled for
DeviceNet communication.

Power-up the module, provide
network power to channel,
and be sure channel is
enabled in both the module
configuration table and
module command word.

Flashing green

the channel is enabled but no
communication is occurring.

Configure scan list table for
channel to add devices.

Solid green

all slave devices in the scan
list table are communicating
normally with the module.

None.

Solid red

the module may be defective.

Reset module. If failures
continue, replace module.

Flashing red

at least one of the slave
devices in the module’s scan
list table has failed to
communicate with the
module.

The network has faulted.

Examine the failed device and
the scan list table for
accuracy.

Module Status
Indicator

Channel 1

Top part of module

Network Status
Indicator

Troubleshooting Your
Module