Configuring the slc controller – Rockwell Automation 2755-SNx Adaptascan Bar Code Readers User Manual

Page 113

Advertising
background image

7–7

Communicating with an SLC on a DH-485 Network

Publication 2755-6.8

This section describes how to configure the SLC 5/04, which is
different than the 5/03.

Using APS and an RS-232 connection, establish an online
connection the Channel 0 port of the SLC 5/04.

When online, change to DH485 protocol and do a WHO ACTIVE
to view the nodes on the network.

For complete details on configuring the SLC 5/04 or 5/03 processors,
refer to the Advanced Programming Software manuals.

SLC 5/04 Configuration

1. Establish communication with the Channel 0 port of the SLC

5/04 using the 1747-CP3/A RS-232 cable.

Default

On line configuration

DF1 Full

F7 1200

Enter (twice)

On line (in RS-232)

2. Verify that you are online in “REM RUN”.

Change configuration driver F2 – PIC

Baud Rate 19,200

Max Node 3

F7 Utility

F5 Channel 0 (Master Mode)

Power down and up

Configuring the SLC
Controller