Downloading Match Codes via DH485 using a PLC-5 Processor and a 2760-RB Module

Publication 2755-6.8

To configure the 2760-RB module:

1. Set all 2760-RB module DIP switches to Off.

2. Connect the smart cable to the Configuration port of the 2760-RB

module and the serial port of the computer.

3. Send a “break sequence” to the 2760-RB module via the Terminal

Emulator:

G. Set the baud rate to 9600, 8 data bits, 1 stop bit, no parity,

no flow control, and either COM1 or COM2 depending on
the smart cable connection.

H. Program a function key to send the “break sequence” by

using the Ctrl-Shift-Break command. (This step is
specifically for Windows 3.1 Terminal Emulation.)

I. Send the break sequence to call up the 2760-RB module

configuration menu.

4. Select menu item 3: Device port protocol names. Set to:

PORT1=COPYRIGHT 1989 ALLEN-BRADLEY COMPANY INC.

2760-SFC2 LAN SERIES A REVISION B (YES/NO)=YES

5. Select menu item 21: Identification numbers. Select:

RS485 LAN 2755-DM6 ASCII MODE 0

H (YES/NO)=YES

6. Select option 11: Configuration parameters. Set to:

SLOT TIME (NO. CHARS) (DEC 0 ... 255) = 15
INTER-CHAR TIME (NO. CHARS) (DEC 0 ... 255) = 7
IDLE TIME (NO. CHARS) (DEC 0 ... 255) = 3

RETRIES (DEC 0 ... 255) = 3
19,200 BITS PER SECOND (YES/NO)=YES
BCD NODE NUMBERS (ENABLE/DISABLE)= ENABLE
BYTE SWAPPING (ENABLE/DISABLE)=ENABLE

RECEIVE MATRIXING (ENABLE/DISABLE)=DISABLE
MATRIX ADDRESS (HEX 0 ... FFFF) = 0
RE-ESTABLISH FREQUENCY (DEC 0 ... 255)=5
POLL FREQUENCY/DESTINATION [0] (HEX 0 ... FFFF)=5

POLL FREQUENCY/DESTINATION [1] (HEX 0 ... FFFF)=105
POLL FREQUENCY/DESTINATION [2] (HEX 0 ... FFFF)=5
POLL FREQUENCY/DESTINATION [3] (HEX 0 ... FFFF)=5

Type save or quit to exit out of the editor.

7. Verify that the 2760-RB is in chassis 0, group 0 module 0.

8. Save the above configuration.