5.3 Fault Detection

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

101

Tr

ou

blesh

oot

ing

5

Digital Operator

Display

Fault Name

Details

Uv3

Undervoltage 3

(Soft-Charge Bypass

Circuit Fault)

The soft-charge bypass circuit failed.

Cause

Possible Solution

The relay or contactor on the soft-charge
bypass circuit is damaged.

• Cycle power to the regenerative unit and see if the fault reoccurs.
• If the problem continues, replace either the control board or the entire regenerative unit. For

instructions on replacing the control board, contact Yaskawa or a Yaskawa representative.

• Check monitor U4-06 for the performance life of the soft-charge bypass.
• Replace either the control board or the entire regenerative unit if U4-06 exceeds 90%. For

instructions on replacing the control board, contact Yaskawa or a Yaskawa representative.

<1> If the fault occurs when starting the regenerative unit, CPF00 or CPF20 is displayed. If it occurs during operation, CPF01 or CPF21 is

displayed.