3.10 Control I/O Connections

64

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

Table 3.11 DIP Switch S1 Settings

Table 3.12 Parameter H3-09 Details

Using the Contact Outputs

Figure 3.29

illustrates the use of multi-function relay outputs and the fault relay outputs.

Figure 3.26

Figure 3.29 Contact Outputs

Setting

Description

V (left position)

Voltage input (-10 to +10 V or 0 to 10 V)

I (right position)

Current input (4 to 20 mA or 0 to 20 mA): default setting

No.

Parameter Name

Description

Setting

Range

Default

Setting

H3-09

Terminal A2 signal level selection

Selects the signal level for terminal A2.
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
3: 0 to 20 mA

0 to 3

2

<1> Minimum load: 5 Vdc, 10 mA

M

M

5

3

4

M

M

6

MA

M1

M2

MB

MC

Relay

SA

SA

Max
250 Vac

Relay

Relay

Relay

Max 250 Vac

Max 250 Vac

Controller

Multi-function relay output

<1>

250 Vac, max. 1 A
30 Vdc, max. 1 A

Fault relay output

<1>

250 Vac, max. 1 A
30 Vdc, max. 1 A

Through mode

Fault

Through mode

Through mode

Regenerative Unit

YAI