B.2 Parameter Tables

172

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

U4-02

(75H)

Number of Run
Commands

RUN Cmd
Counter

Displays the number of times the Run command is entered. Reset the
number of Run commands using parameter o4-13. This value will reset to
0 and start counting again after reaching 65535.

No signal
output
available

1 time

U4-03

(67H)

<5>

Cooling Fan
Operation Time

Fan
Elapsed
TIme

Displays the cumulative operation time of the cooling fan. The default
value for the fan operation time is reset in parameter o4-03. This value will
reset to 0 and start counting again after reaching 99999.

No signal
output
available

1 h

U4-04
(7EH)

Cooling Fan
Maintenance

Fan Life
Mon

Displays main cooling fan usage time as a percentage of its expected
performance life. Parameter o4-03 can be used to reset this monitor.
Replace the fan when this monitor reaches 90%.

No signal
output
available

1%

U4-05
(7CH)

Capacitor
Maintenance

Cap Life
Mon

Displays main circuit capacitor usage time as a percentage of their
expected performance life. Parameter o4-05 can be used to reset this
monitor.
Replace the capacitor when this monitor reaches 90%.

No signal
output
available

1%

U4-06

(7D6H)

Soft Charge
Bypass Relay
Maintenance

ChgCirc
Life Mon

Displays the soft charge bypass relay maintenance time as a percentage of
its estimated performance life. Parameter o4-07 can be used to reset this
monitor.
Replace the soft charge bypass relay when this monitor reaches 90%.

No signal
output
available

1%

U4-08

(68H)

Heatsink
Temperature

Heatsink
Temp

Displays the heatsink temperature.

10 V: 100

°C

1

°C

U4-09
(5EH)

LED Check

LED Oper
Check

Lights all segments of the LED to verify that the display is working
properly.

No signal
output
available

U4-13

(7CFH)

Peak Hold
Current

Current
PeakHold

Displays the highest current value that occurred during run.

No signal
output
available

1 A

U6: Operation Status Monitors

U6-80 to

U6-99

(7B0H to

7F9H)

Option Monitors
1 to 20

Shows the monitor information for Option Monitor 1 (876 hex) to 20 (8FF
hex).
This information is displayed when option cards are connected.
200 V Class: 100% = 400 Vdc
400 V Class: 100% = 800 Vdc

No signal
output
available

U9: Operation Status Monitors

U9-04

(823H)

Regenerative
Power (GWh)

GWh
Produced

Shows the total amount of regenerated power.

0 to 999

1 GWh

U9-05

(824H)

Regenerative
Power (MWh)

MWh
Produced

0 to 999

1 MWh

U9-06

(825H)

Regenerative
Power (kWh)

kWh
Produced

0 to 999

1 kWh

U9-11 to

U9-14

(82AH to

82DH)

Regenerative
Power
Rates 1 to 4

Produced
† ($)

These parameters show the regenerative power rate in Power Unit Price
(o4-19) that is calculated from the total electrical power consumptions in
U9-04 to U9-06.

The unit price is set in o4-19, and U9-11 to U9-14 are U9-04 to U9-06
times o4-19.

0 to 999

<4> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 0099H.

<5> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 009BH.

No.

(Address

Hex)

Name

LCD

Display

Description

Analog

Output

Level

Unit

000 000 000 kWh

U9-06

U9-05

U9-04

000 000 000 000

U9-14

U9-13

U9-12

U9-11

TOEP_C710656_08B_1_0.book 172 ページ 2015年2月5日 木曜日 午前10時7分

Advertising