B.2 Parameter Tables
172
YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
U4-02
(75H)
Number of Run
Commands
RUN Cmd
Counter
Displays the number of times the Run command is entered. Reset the
number of Run commands using parameter o4-13. This value will reset to
0 and start counting again after reaching 65535.
No signal
output
available
1 time
U4-03
(67H)
Cooling Fan
Operation Time
Fan
Elapsed
TIme
Displays the cumulative operation time of the cooling fan. The default
value for the fan operation time is reset in parameter o4-03. This value will
reset to 0 and start counting again after reaching 99999.
No signal
output
available
1 h
U4-04
(7EH)
Cooling Fan
Maintenance
Fan Life
Mon
Displays main cooling fan usage time as a percentage of its expected
performance life. Parameter o4-03 can be used to reset this monitor.
Replace the fan when this monitor reaches 90%.
No signal
output
available
1%
U4-05
(7CH)
Capacitor
Maintenance
Cap Life
Mon
Displays main circuit capacitor usage time as a percentage of their
expected performance life. Parameter o4-05 can be used to reset this
monitor.
Replace the capacitor when this monitor reaches 90%.
No signal
output
available
1%
U4-06
(7D6H)
Soft Charge
Bypass Relay
Maintenance
ChgCirc
Life Mon
Displays the soft charge bypass relay maintenance time as a percentage of
its estimated performance life. Parameter o4-07 can be used to reset this
monitor.
Replace the soft charge bypass relay when this monitor reaches 90%.
No signal
output
available
1%
U4-08
(68H)
Heatsink
Temperature
Heatsink
Temp
Displays the heatsink temperature.
10 V: 100
°C
1
°C
U4-09
(5EH)
LED Check
LED Oper
Check
Lights all segments of the LED to verify that the display is working
properly.
No signal
output
available
–
U4-13
(7CFH)
Peak Hold
Current
Current
PeakHold
Displays the highest current value that occurred during run.
No signal
output
available
1 A
U6: Operation Status Monitors
U6-80 to
U6-99
(7B0H to
7F9H)
Option Monitors
1 to 20
–
Shows the monitor information for Option Monitor 1 (876 hex) to 20 (8FF
hex).
This information is displayed when option cards are connected.
200 V Class: 100% = 400 Vdc
400 V Class: 100% = 800 Vdc
No signal
output
available
–
U9: Operation Status Monitors
U9-04
(823H)
Regenerative
Power (GWh)
GWh
Produced
Shows the total amount of regenerated power.
0 to 999
1 GWh
U9-05
(824H)
Regenerative
Power (MWh)
MWh
Produced
0 to 999
1 MWh
U9-06
(825H)
Regenerative
Power (kWh)
kWh
Produced
0 to 999
1 kWh
U9-11 to
U9-14
(82AH to
82DH)
Regenerative
Power
Rates 1 to 4
Produced
($)
These parameters show the regenerative power rate in Power Unit Price
(o4-19) that is calculated from the total electrical power consumptions in
U9-04 to U9-06.
The unit price is set in o4-19, and U9-11 to U9-14 are U9-04 to U9-06
times o4-19.
0 to 999
–
<4> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 0099H.
<5> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 009BH.
No.
(Address
Hex)
Name
LCD
Display
Description
Analog
Output
Level
Unit
000 000 000 kWh
U9-06
U9-05
U9-04
000 000 000 000
U9-14
U9-13
U9-12
U9-11