B.2 Parameter Tables

156

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

b: Application

Application parameters configure the source of the operation mode selection.

No.

(Address

Hex)

Name

LCD Display

Description

Values

b1: Operation Mode Selection

b1-02

(181H)

Run Command
Selection 1

Run Source 1
0: Digital operator
1: Digital Inputs
2: Communication
3: Option PCB

0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option PCB

Default: 1
Range: 0 to 3

b1-06

(185H)

Digital Input
Reading

Cntl Input Scans
1: Scan
2: Scans

Defines how the digital inputs are read. The inputs are
acted upon every 1 ms or 2 ms depending upon the setting.
0: Input status is read once and processed immediately (for
quicker response)
1: Input is read twice and processed only if the status is the
same in both readings (robust against noisy signals)

Default: 1
Range: 0, 1

b1-08

(187H)

Run Command
Selection in
Programming Mode

RUN dur PRG Mode
0: Run
Disabled@PRG
1: ModeRun
Enabled@PRG
2: Prg only @ Stop

Allow the regenerative unit to run while in Programming
Mode.
0: Run command is not accepted while in Programming
Mode.
1: Run command is accepted while in Programming Mode.
2: Prohibit entering Programming Mode during run.

Default: 0
Range: 0 to 2

b1-17

(1C6H)

Run Command at
Power Up

Run Cmd @ Pwr On
0: Cycle Ext Run
1: Accept Ext Run

Determines whether an external Run command that is
active during power up will start the regenerative unit.
0: Disregarded. A new Run Command must be issued.
1: Allowed. Regenerative unit will start immediately if
Run Command is present at power up.

Default: 0
Range: 0, 1

b1-21

(766H)

Operator Operation
Mode

Run Mode Sel
0: Manual Run
1: Auto run

Sets the operation mode when b1-02 (Run Command
Selection) is set to 0 (LED operator or LCD operator).
0: Forced operation
1: Automatic operation

Default: 1
Range: 0, 1

b4: Timer Function

b4-01

(1A3H)

Timer Function
On-Delay Time

Delay-ON Timer

Sets the on-delay times for a digital timer output
(H2-††=12).
The output is triggered by a digital input programmed to
H1-††=18.

Default: 0.0 s
Min.: 0.0 s
Max.: 3000.0 s

b4-02

(1A4H)

Timer Function
Off-Delay Time

Delay-OFF Timer

Sets the off-delay times for a digital timer output
(H2-††=12).
The output is triggered by a digital input programmed to
H1-††=18.

Default: 0.0 s
Min.: 0.0 s
Max.: 3000.0 s