YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

129

Per

iodic Ins

pec

tion

&

Maint

ena

nc

e

6

Cooling Fan Wiring: 2A0073, 4A0105, 4A0150

1.

Position the protective tube so the fan connector sits in the center of the protective tube.

2.

Insert the connector for fan B2 and guide the lead wire for fan B2 so the cable hook holds it in place. Insert the
connector for fan B1.

Figure 6.17

Figure 6.17 Cooling Fan Wiring: 2A0073, 4A0105, 4A0150

3.

Double-check the relay connector to ensure it is properly connected.

Cooling Fan Wiring: 2A0105, 4A0210 to 4A0300

1.

Position the protective tube so the fan connector sits in the center of the protective tube.

2.

In the space between fans 1 and 2, place the fan connector for fan B2 in front of the fan connector for fan B1.

3.

Place the connector for fan B3 between fans B2 and B3.

Note: Model 2A0105 does not have the fan B3.

Figure 6.18

Figure 6.18 Cooling Fan Wiring: 2A0053 to 2A0105, 4A0053 to 4A0300

Protective tube

次回用

Cable Hook

Connector for fan B2

Connector for fan B1

Fan B2

Fan B1

D1000

Protective tube

Cable cover

Connector for
fan B2

Connector for
fan B3

Fan B2

Fan B1

Connector for
fan B1

Fan B3