6.4 Cooling Fans

124

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

Installing the Cooling Fan

Reverse the procedure described above to reinstall the cooling fan.

1.

Install the replacement cooling fan into the regenerative unit, ensuring the alignment pins line up as shown in the
figure below.

Figure 6.4

Figure 6.4 Install the Cooling Fan: 2A03P5 to 2A0028, 4A03P5 to 4A0028

2.

Properly connect the fan power lines, then place the cable back into the recess of the regenerative unit.

Figure 6.5

Figure 6.5 Connect the Cooling Fan Power Supply Connectors: 2A03P5 to 2A0028, 4A03P5 to 4A0028

3.

While pressing in on the hooks on the front side of the fan finger guard, guide the fan finger guard until it clicks
back into place.

Figure 6.6

Figure 6.6 Reattach the Fan Finger Guard: 2A03P5 to 2A0028, 4A03P5 to 4A0028

4.

Turn on the power supply and set o4-03 to 0 to reset the Maintenance Monitor cooling fan operation time.

A – Push the connectors

together so no space
remains between them

C – Make sure the alignment

pins line up properly

B – Label facing up

B

C

A

R1000

R1000

R1000

TOEP_C710656_08B_1_0.book 124 ページ 2015年2月5日 木曜日 午前10時7分