U: monitors, U1 - 10, U1 - 11 – Yaskawa R1000 Series Power Regenerative Unit User Manual

Page 168

Advertising
background image

B.2 Parameter Tables

168

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

U: Monitors

Monitor parameters allow the user to view regenerative unit status, fault information, and other data concerning
regenerative unit operation.

o4-12

(512H)

kWh Monitor
Initialization

kWh Monitor Init
0: No Reset
1: Reset

0: U4-10 and U4-11 monitor data is not reset when the
regenerative unit is initialized (A1-03).
1: U4-10 and U4-11 monitor data is reset when the
regenerative unit is initialized (A1-03).

Default: 0
Min.: 0
Max.: 1

o4-13

(528H)

Number of Run
Commands Counter
Initialization

Run Counter Init
0: No Reset
1: Reset

0: Number of Run commands counter is not reset when the
regenerative unit is initialized (A1-03).
1: Number of Run commands counter is reset when the
regenerative unit is initialized (A1-03).

Default: 0
Min.: 0
Max.: 1

o4-19

(113AH)

Power Unit Price

Cost per 1 kWh

This parameter is used to calculate the power rate that is
displayed for User Monitors U9-07 through U9-14.
Set the price per 1 kWh.

Default: 000.00
Min.: 000.00
Max.: 650.00

<7> Parameter is available in software versions PRG: 2003 and later.

No.

(Address

Hex)

Name

LCD

Display

Description

Analog

Output

Level

Unit

U1: Operation Status Monitors

U1-10

(49H)

Input Terminal
Status

Input Term
Sts

Displays the input terminal status.

No signal
output
available

U1-11

(4AH)

Output Terminal
Status

Output
Term Sts

Displays the output terminal status.

No signal
output
available

No.

(Address

Hex)

Name

LCD Display

Description

Values

U1 - 10=

0 0 0 0 0 0 0 0

Digital input 1
(terminal S1 enabled)

Digital input 2
(terminal S2 enabled)

Digital input 3
(terminal S3 enabled)

Digital input 4
(terminal S4 enabled)

Digital input 5
(terminal S5 enabled)

Digital input 6
(terminal S6 enabled)

Digital input 7
(terminal S7 enabled)

Digital input 8
(terminal S8 enabled)

1: ON 0: OFF

U1 - 11=

0 0 0 0 0 0 0 0

Multi-Function Relay Output
(terminal M1-M2)

Multi-Function Relay Output
(terminal M3-M4)

Multi-Function Relay Output
(terminal M5-M6)

Reserved

Fault Relay
(terminal MA/MB-MC closed
MA/MB-MC open)

1: ON 0: OFF

YAI