5.3 Fault Detection

92

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

Digital Operator

Display

Fault Name

Details

CE

MEMOBUS/Modbus

Communication Error

Control data was not received for the CE detection time set to H5-09.

Cause

Possible Solution

Faulty communications wiring or an existing
short circuit.

Check for faulty wiring.

• Correct the wiring.
• Check for disconnected cables and short circuits and repair as needed.

Communication data error occurred due to
noise.

Check the various options available to minimize the effects of noise.

• Counteract noise in the control circuit, main circuit, and ground wiring.
• Use only recommended cables or other shielded line. Ground the shield on the controller side

or the regenerative unit input power side.

• Ensure that other equipment such as switches or relays do not cause noise. Use surge

suppressors if required.

• Separate all communication wiring from drive power lines. Install an EMC noise filter to the

regenerative unit power supply input.

Digital Operator

Display

Fault Name

Details

CoF

Current Offset Fault

A fault occurred in adjustment of the automatic current offset when the power supply was turned
on.

Cause

Possible Solution

An error occurred in the power supply detection
circuit.

Cycle the power supply and check operation.
If the fault occurs again, replace the board or regenerative unit. For information on board
replacement, consult with your Yaskawa representative or the nearest Yaskawa sales office.

Digital Operator

Display

Fault Name

Details

,

CPF00,

CPF01

<1>

Control Circuit Error A fault occurred in the control circuit.

to CPF11 to

CPF22

<1>

to CPF26 to

CPF35

Cause

Possible Solution

There is a self-diagnostic error in the control
circuit.

• Cycle power to the regenerative unit.
• If the problem continues, replace the control board or the entire regenerative unit. Contact

Yaskawa or a Yaskawa representative for instructions on replacing the control board.

Connector on the operator is damaged.

Replace the operator.

Digital Operator

Display

Fault Name

Details

CPF02

A/D Conversion Error An A/D conversion error or control circuit error occurred.

Cause

Possible Solution

Control circuit is damaged.

Cycle power to the regenerative unit.
If the problem continues, replace the control board or the entire regenerative unit. Contact
Yaskawa or a Yaskawa representative for instructions on replacing the control board.

Digital Operator

Display

Fault Name

Details

CPF03

Control Board

Connection Error

Connection error between the control board and the regenerative unit

Cause

Possible Solution

There is a connection error.

Turn off the power and check the connection between the control board and the regenerative unit.
If the problem continues, replace the control board or the entire regenerative unit. Contact
Yaskawa or a Yaskawa representative for instructions on replacing the control board.