C.4 MEMOBUS/Modbus Setup Parameters

180

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

H5-04: Stopping Method after Communication Error

Selects the stopping method after a communications error (CE) has occurred.

Setting 1: Stop operation
Setting 3: Alarm only (continue operation)

H5-05: Communication Fault Detection Selection

Enables or disables the CE detection for communications.

Setting 0: Disabled

No communication error detection. The regenerative unit continues operation.

Setting 1: Enabled

If the regenerative unit does not receive data from the master for longer than the time set to H5-09, then a CE fault will be
triggered and the regenerative unit will operate as determined by parameter H5-04.

H5-06: Drive Transmit Wait Time

Sets the time the regenerative unit waits after receiving data from a master until responding data.

Figure C.4

Figure C.4 Regenerative Unit Transmit Wait Time Setting

H5-07: RTS Control Selection

Enables or disables RTS control.

Setting 0: Disabled. RTS is always on.

Use this setting with point-to-point or multi-drop RS-422 communications.

Setting 1: Enabled. RTS switches while sending.

Use this setting when using RS-485 signals for communications or when using the RS-422 signals for point-to-point
communications.

H5-09: Communications Fault Detection Time

Sets the time the communications must be lost before the regenerative unit triggers a CE fault.

No.

Name

Setting Range

Default

H5-04

Stopping Method after CE

1, 3

3

No.

Name

Setting Range

Default

H5-05

Communication Fault Detection Selection

0 or 1

1

No.

Name

Setting Range

Default

H5-06

Drive Transmit Wait Time

5 to 65 ms

5 ms

No.

Name

Setting Range

Default

H5-07

RTS Control Selection

0 or 1

1

No.

Name

Setting Range

Default

H5-09

Communications Fault Detection Time

0.0 to 10.0 s

2.0 s

Command message

Response message

Command message

PLC

→Regenerative Unit

PLC

→Regenerative Unit

Regenerative Unit

→PLC

Time

24 bit length

H5-06 setting

24 bit length

5 ms

D1000