U1 - 12, U1 - 19 – Yaskawa R1000 Series Power Regenerative Unit User Manual

Page 169

Advertising
background image

B.2 Parameter Tables

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

169

Par

ame

te

r Li

st

B

U1-12
(4BH)

Drive Status

Int Ctl Sts 1

Verifies the regenerative unit operation status.

No signal
output
available

U1-13
(4EH)

Terminal A1 Input
Level

Term A1
Level

Displays the signal level to analog input terminal A1.

10 V: 100%

0.1%

U1-14

(4FH)

Terminal A2 Input
Level

Term A2
Level

Displays the signal level to analog input terminal A2.

10 V: 100%

0.1%

U1-15

(50H)

Terminal A3 Input
Level

Term A3
Level

Displays the signal level to analog input terminal A3.

10 V: 100%

0.1%

U1-18

(61H)

oPE Fault
Parameter

OPE Error
Code

Displays the parameter number that caused the oPE02 or oPE08 operation
error.

No signal
output
available

U1-19

(66H)

MEMOBUS/
Modbus Error
Code

Transmit
Err

Displays the contents of a MEMOBUS/Modbus error.

No signal
output
available

U1-25
(4DH)

Software Number
(Flash)

CPU 1 SW
Number

FLASH ID

No signal
output
available

U1-26
(5BH)

Software No.
(ROM)

CPU 2 SW
Number

ROM ID

No signal
output
available

U1-27

(7A8H)

Message ID
(OPR)

MessageID
(OPR)

Shows the message ID number for OPE.

No signal
output
available

U1-28

(7A9H)

Message ID
(INV)

MessageID
(INV)

Shows the message ID number for INV.

No signal
output
available

U1-52

(1081H)

DC Bus Voltage
Feedback

DC V
Feedback

Shows the DC bus voltage feedback value.

200 V Class

10 V: 400 V

400 V Class

10 V: 800 V

1 V

U1-54

(1083H)

Power Supply
Voltage

AC Voltage Shows the power supply voltage.

200 V Class

10 V: 400 V

400 V Class

10 V: F800 V

1 V

U1-55

(1084H)

Power Supply
Current

AC Current Shows the current on the power supply side.

10 V: Rated
Input Current

1 A

No.

(Address

Hex)

Name

LCD

Display

Description

Analog

Output

Level

Unit

U1 - 12=

0 0 0 0 0 0 0 0

Bit 0: During RUN

Bit 1: Reserved

Bit 2: Reserved

Bit 3: Fault reset signal input

Bit 4: Power supply established
(0: Not completed, 1: Completed)

Bit 5: Operation ready

Bit 6: Minor fault detected

Bit 7: Fault detected

YAI

U1 - 19=

0 0 0 0 0 0 0 0

CRC Error

Data Length Error

Not Used

Parity Error

Overrun Error

Framing Error

Timed Out

Not Used

1
1

0
1
1
1
1
0

TOEP_C710656_08B_1_0.book 169 ページ 2015年2月5日 木曜日 午前10時7分