Yaskawa R1000 Series Power Regenerative Unit User Manual

Page 161

Advertising
background image

B.2 Parameter Tables

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

161

Par

ame

te

r Li

st

B

8

During baseblock (N.O.)

BaseBlk 1

Closed: Regenerative unit has entered the baseblock state (no
regeneration).

E

Fault

Fault

Closed: Fault occurred.

F

Through mode

Not Used

Set this value when using the terminal in the pass-through mode.

10

Minor fault

Minor Fault

Closed: An alarm has been triggered.

11

Fault reset command active

Reset Cmd Active

Closed: A command has been entered to clear a fault via the input
terminals or from the serial network.

12

Timer output

Timer Output

Closed: Timer output.

1B

During baseblock (N.C.)

BaseBlk 2

Open: Regenerative unit has entered the baseblock state (no
regeneration).

1D

During Regeneration

Regenerating

Closed: Motor is regenerating energy into the regenerative unit.

1E

Restart enabled

Dur Flt Restart

Closed: An automatic restart is performed

20

Heatsink Overheat (oH)
pre-alarm

OH Prealarm

Closed: Heatsink temperature exceeds the parameter L8-02 value.

24

Fuse Blowout Detection

FUA/FUD Detect

Closed: Fuse burnout detected.

25

During Run 1

During RUN 1

Closed: The drive is ready to operate.

26

During MC ON

MC On

Closed: The magnetic contactor is closed.

27

Overload (oL2) Warning

OL2 Pre-alarm

Closed: There is an overload warning.

2F

Maintenance Period

Maintenance

Closed: It is time to perform maintenance on the cooling fan, electrolytic
capacitor, and inrush prevention relay.

3A

kWh Monitor Pulse Output Power

(Produced)

Set the unit in H2-06.
Multi-function output is ON for 200 ms depending on the unit selected in
H2-06.

3B

Alarm 2

Minor Fault 2

Closed: Alarm occurred (excluding Uv, AUv, Fdv, SrC, and PAUv).
Note: This setting is available in regenerative unit software versions
PRG:2003 or later.

3C

LOCAL/REMOTE status

Local

Open: REMOTE
Closed: LOCAL

4D

oH Pre-alarm time limit

OH Pre-Alarm

Closed: oH pre-alarm time limit has passed.

60

Internal cooling fan alarm

Fan Alrm Det

Closed: Internal cooling fan alarm

100 to 160

Function 0 to 60 with inverse
output

Inverts the output switching of the multi-function output functions.
Set the last two digits of 1†† to reverse the output signal of that
specific function.

No.

(Address

Hex)

Name

LCD Display

Description

Values

H3: Multi-Function Analog Inputs

H3-01

(410H)

Terminal A1 Signal
Level Selection

Term A1 Level
0: 0-10V, (LowLim=0)
1: 0-10V, (BipolRef)

0: 0 to 10 V
1: -10 to 10 V

Default: 0
Min.: 0
Max.: 1

H3-02

(434H)

Terminal A1
Function Selection

Term A1 FuncSel

Sets the function of terminal A1.

Default: F
Min.: F
Max.: F

H3-03

(411H)

Terminal A1 Gain
Setting

Terminal A1 Gain

Sets the level of the input value selected in H3-02 when 10
V is input at terminal A1.

Default: 100.0%
Min.: -999.9%
Max.: 999.9%

H3-04

(412H)

Terminal A1 Bias
Setting

Terminal A1 Bias

Sets the level of the input value selected in H3-02 when 0
V is input at terminal A1.

Default: 0.0%
Min.: -999.9%
Max.: 999.9%

H2 Multi-Function Relay Output Settings

H2-……

Setting

Function

LCD Display

Description