C.6 Communications Timing

To prevent a communications overrun in the slave regenerative unit, the master should wait a certain time between
sending messages to the same regenerative unit. In the same way, the slave regenerative unit must wait before sending
response messages to prevent an overrun in the master. This section explains the message timing.

Command Messages from Master to Regenerative Unit

The master must wait for a specified time between receiving a response and resending the same type of command to the
same slave regenerative unit to prevent overrun and data loss. The minimum wait time depends on the command as
shown in

Table C.3

.

Table C.3 Minimum Wait Time for Sending Messages

Figure C.5

Figure C.5 Minimum Wait Time for Sending Messages

Set a timer in the master to check how long it takes for the slave regenerative unit (s) to respond to the master. If no
response is received within a certain amount of time, the master should try resending the message.

Response Messages from Regenerative Unit to Master

If the slave regenerative unit receives a command from the master, it will process the data received and wait for the time
set in H5-06 until it responds. Increase H5-06 if the regenerative unit response causes overrun in the master.

Figure C.6

Figure C.6 Minimum Response Wait Time

Command Type

Example

Minimum Wait Time

1

<1> If the regenerative unit receives command type 1 data during the minimum wait time, it will perform the command and then respond. However,

if it receives a command type 2 or 3 during that time, either a communication error will result or the command will be ignored.

• Control command (Run, Stop)
• Set inputs/outputs
• Read monitors and parameter values

5 ms

<1>

2

Write parameters

H5-11 = 0: 50 ms

H5-11 = 1: 200 ms

<1>

3

Save changes using an Enter command

200 ms to 2 s, depending on the number

of parameters that were changed

<1>

24 bit length

Regenerative Unit

Regenerative Unit

Regenerative Unit

Command message

Response message

Command message

Time

Master Send
Wait Time

PLC

PLC

→PLC

D1000

Command message

Response message

Command message

PLC

→Regenerative Unit

PLC

→Regenerative Unit

Regenerative Unit

→PLC

24 bit length

H5-06
setting

Time

D1000