Yaskawa R1000 Series Power Regenerative Unit User Manual

Page 103

Advertising
background image

5.4 Alarm Detection

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

103

Tr

ou

blesh

oot

ing

5

Digital Operator

Display

Minor Fault Name

Detail

Alarm Output

(H2-†† = 10)

bUS

Option Communication

Error

• The connection was lost after initial communication was established.
• Assign a Run command frequency reference to the option.

YES

Cause

Possible Solutions

Connection is broken or master controller
stopped communicating.

• Check for faulty wiring.
• Correct the wiring.
• Check for disconnected cables and short circuits. Repair as needed.

Option is damaged.

If there are no problems with the wiring and the fault continues to occur, replace the option.

The option is not properly connected to the
regenerative unit.

• The connector pins on the option are not properly lined up with the connector pins on the

regenerative unit.

• Reinstall the option.

A data error occurred due to noise.

• Check options available to minimize the effects of noise.
• Take steps to counteract noise in the control circuit wiring, main circuit lines and ground

wiring.

• Try to reduce noise on the controller side.
• Use surge absorbers on magnetic contactors or other equipment causing the disturbance.
• Use recommended cables or some other type of shielded line. Ground the shield to the

controller side or on the input power side.

• Separate the wiring for communication devices from the regenerative unit input power lines.

Install an EMC noise filter to the regenerative unit input power.

Digital Operator

Display

Minor Fault Name

Detail

Alarm Output

(H2-†† = 10)

CALL

Serial Communication

Transmission Error

Communication has not yet been established.

YES

Cause

Possible Solutions

Communications wiring is faulty, there is a
short circuit, or something is not connected
properly.

• Check for wiring errors.
• Correct the wiring.
• Check for disconnected cables and short circuits. Repair as needed.

Programming error on the master side.

Check communications at start-up and correct programming errors.

Communications circuitry is damaged.

• Perform a self-diagnostics check.
• If the problem continues, replace either the control board or the entire regenerative unit. For

instructions on replacing the control board, contact Yaskawa or your nearest sales representative.

Termination resistor setting is incorrect.

Install a termination resistor at both ends of a communication line. Set the internal termination
resistor switch correctly on slave regenerative units. Place DIP switch S2 to the ON position.

Digital Operator

Display

Minor Fault Name

Detail

Alarm Output

(H2-†† = 10)

CE

MEMOBUS/Modbus

Communication Error

Control data was not received correctly for two seconds.

YES

Cause

Possible Solutions

A data error occurred due to noise.

• Check options available to minimize the effects of noise.
• Take steps to counteract noise in the control circuit wiring, main circuit lines, and ground

wiring.

• Reduce noise on the controller side.
• Use surge absorbers for the magnetic contactors or other components that may be causing the

disturbance.

• Use only recommended shielded line. Ground the shield on the controller side or on the

regenerative unit input power side.

• Separate all wiring for communication devices from regenerative unit input power lines. Install

an EMC noise filter to the regenerative unit input power supply.

Communication protocol is incompatible.

• Check the H5 parameter settings and the protocol setting in the controller.
• Ensure settings are compatible.

The CE detection time (H5-09) is set shorter
than the time required for a communication
cycle to take place.

• Check the PLC.
• Change the software settings in the PLC.
• Set a longer CE detection time using parameter H5-09.

Incompatible PLC software settings or there is
a hardware problem.

• Check the PLC.
• Remove the cause of the error on the controller side.

Communications cable is disconnected or
damaged.

• Check the connector to make sure the cable has a signal.
• Replace the communications cable.

TOEP_C710656_08B_1_0.book 103 ページ 2015年2月5日 木曜日 午前10時7分