2.2 Mechanical Installation
26
YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
■
Single Regenerative Unit Installation
shows the installation distance required to maintain sufficient space for airflow and wiring. Install the heatsink
against a closed surface to avoid diverting cooling air around the heatsink.
Figure 2.2
Figure 2.2 Correct Installation Spacing (Single)
■
Parallel Mounting with Drive
When installing the regenerative unit beside a drive, mount the devices according to
.
Figure 2.3
Figure 2.3 Space Between Regenerative Unit and Drive (Parallel Mounting)
A – 50 mm minimum
C – 120 mm minimum
B – 30 mm minimum
D – Airflow direction
A – 50 mm minimum
C – 60 mm minimum
B – 30 mm minimum
D – 120 mm minimum
Side Clearance
Top/Bottom Clearance
A
A
C
C
B
B
D
D
YAI
A
A
A
A
B
C
Drive
Regenerative Unit
B
Line up the tops of the drive and regenerative unit.
Side Clearance
D
D
Top/Bottom Clearance