D.4 CSA Standards Compliance

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

219

St

and

ar

ds Co

mpl

ia

nce

D

D.4 CSA Standards Compliance

Conditions of Acceptability

Refer to

Conditions of Acceptability on page 207

.

Installing Standard Configuration Devices

Refer to

Standard Configuration Devices on page 204

for details on the standard configuration devices.

Main Circuit Terminal Wiring

Yaskawa recommends using closed-loop crimp terminals on all regenerative unit models. To maintain UL/cUL or CSA
approval, UL Listed or CSA Certified closed-loop crimp terminals are specifically required when wiring the regenerative
unit main circuit terminals on models 2A0035 to 2A0105, 4A0035 to 4A0300. Use only the tools recommended by the
terminal manufacturer for crimping. Refer to

Closed-Loop Crimp Terminal Recommendations on page 212

for

closed-loop crimp terminal recommendations. The wire gauges listed in the following tables are Yaskawa
recommendations. Refer to local codes for proper wire gauge selections.

Low Voltage Wiring for Control Circuit Terminals

The external power supply shall be a CSA certified or cUL Listed Class 2 power source only or equivalent. Refer to

Table D.5

for details.

CSA for Industrial Control Equipment

The R1000 is CSA certified as Industrial Control Equipment Class 3211.

Specifically, the R1000 is certified to: CAN/CSA C22.2 No.0-10 and CAN/CSA C22.2 No.14-13.

Figure D.5

Figure D.5 CSA Mark

CSA for Elevator Equipment

The R1000 is tested and complies with CSA B44.1-11/ASME A17.5-2011 standard.

This standard is used by CSA to evaluate the R1000 to Class 2411 (Elevator Equipment).

Figure D.6

Figure D.6 CSA B44.1-11/ASME A17.5-2011 Mark