5.3 Fault Detection

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

97

Tr

ou

blesh

oot

ing

5

Digital Operator

Display

Fault Name

Details

oFb02

Option Card Fault at

Option Port CN5-B

Same type of option card is currently connected

Cause

Possible Solution

An option card of the same type is already
installed in option port CN5-A.

Only one of each option card type can only be installed simultaneously. Make sure only one type
of option card is connected.

Digital Operator

Display

Fault Name

Details

to

oFb03 to

oFb11

Option card error

occurred at Option Port

CN5-B

There is a fault in the option card.

to

oFb12 to

oFb17

Option card error

occurred at Option Port

CN5-B

Cause

Possible Solution

Option card or hardware is damaged.

• Cycle power to the regenerative unit.
• If the problem continues, replace the control board or the entire regenerative unit. Contact

Yaskawa or a Yaskawa representative for instructions on replacing the control board.

Digital Operator

Display

Fault Name

Details

oFC00

Option Card

Connection Error at

Option Port CN5-C

Option compatibility error

Cause

Possible Solution

The option card installed into port CN5-C is
incompatible with the regenerative unit.

Confirm that the regenerative unit supports the option card to be installed. Contact Yaskawa for
assistance.

Digital Operator

Display

Fault Name

Details

oFC01

Option Card Fault at

Option Port CN5-C

Option not properly connected

Cause

Possible Solution

The option card connection to port CN5-C is
faulty.

Turn the power off and reconnect the option card.

Digital Operator

Display

Fault Name

Details

oFC02

Option Card Fault at

Option Port CN5-C

Same type of option card is currently connected

Cause

Possible Solution

An option card of the same type is already
installed in option port CN5-A or CN5-B.

Only one of each option card type can only be installed simultaneously. Make sure only one type
of option card is connected.

Digital Operator

Display

Fault Name

Details

to

oFC03 to

oFC11

Option Card Error

Occurred at Option

Port CN5-C

There is a fault in the option card.

to

oFC12 to

oFC17

Option Card Error

Occurred at Option

Port CN5-C

Cause

Possible Solution

Option card or hardware is damaged.

• Cycle power to the regenerative unit.
• If the problem continues, replace the control board or the entire regenerative unit. Contact

Yaskawa or a Yaskawa representative for instructions on replacing the control board.