Yaskawa R1000 Series Power Regenerative Unit User Manual

Page 165

Advertising
background image

B.2 Parameter Tables

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

165

Par

ame

te

r Li

st

B

L5: Fault Restart

L5-01

(49EH)

Number of Auto
Restart Attempts

Num of Restarts

Sets the number of times the regenerative unit may attempt
to restart after the following faults occur: oC, oH1, oL2,
ov, Uv1.

Default: 0 time
Min.: 0 time
Max.: 10 times

L5-02

(49FH)

Auto Restart Fault
Output Operation
Selection

Restart Sel
0: Flt Outp Disabld
1: Flt Outp Enabled

0: Fault output not active.
1: Fault output active during restart attempt.

Default: 0
Min.: 0
Max.: 1

L5-04

(4A0H)

Fault Reset Interval
Time

Flt Reset Wait T

Sets the amount of time to wait between performing fault
restarts.

Default: 10.0 s
Min.: 0.5 s
Max.: 600.0 s

L5-05

(46CH)

Fault Reset
Operation Selection

Fault Reset Sel
0: Continuous
1: Use L5-04 Time

0: Continuously attempt to restart while incrementing
restart counter only at a successful restart.
1: Attempt to restart with the interval time set in L5-04 and
increment the
restart counter with each attempt.

Default: 0
Min.: 0
Max.: 1

L8: Drive Protection

L8-02

(4AEH)

Overheat Alarm
Level

OH Pre-Alarm Lvl

An overheat alarm occurs when heatsink temperature
exceeds the L8-02 level.

Default:

<2>

Min.: 50

°C

Max.: 150

°C

L8-03

(4AFH)

Overheat Pre-Alarm
Operation Selection

OH Pre-Alarm Sel
0: Ramp to stop
3: Alarm only

0: Ramp to stop. A fault is triggered.
3: Continue operation. An alarm is triggered.

Default: 3
Min.: 1
Max.: 3

L8-07

(4B3H)

Input Phase Loss
(PF3) Protection
Selection

Phase Loss Det

0: Disabled
1: Enabled

Default: 1
Min.: 0
Max.: 1

L8-10

(4B6H)

Heatsink Cooling
Fan Operation
Selection

Fan On/Off Sel
0: Dur Run (OffDly)
1: Always On

0: During run only. Fan operates only during run for L8-11
seconds after stop.
1: Fan always on. Cooling fan operates whenever the
regenerative unit is powered up.

Default: 0
Min.: 0
Max.: 1

L8-11

(4B7H)

Heatsink Cooling
Fan Off Delay Time

Fan Delay Time

Sets a delay time to shut off the cooling fan after the Run
command is removed when L8-10 = 0.

Default: 60 s
Min.: 0 s
Max.: 300 s

L8-12

(4B8H)

Ambient
Temperature Setting

Ambient Temp

Enter the ambient temperature. This value adjusts the oL2
detection level.

Default: 40

°C

Min.: -10

°C

Max.: 50

°C

L8-35

(4ECH)

Installation Method
Selection

Installation Sel
0: IP00/OpenChassis
1: Side-by-Side
2: IP20/NEMA Type 1
3: ExternalHeatsink

0: IP00 Open Type Enclosure
1: Side-by-Side Mounting
2: IP20/NEMA Type 1
3: External Heatsink Installation

Default:

<2>

Min.: 0
Max.: 3

L8-41

(4F2H)

High Current Alarm
Selection

High Cur Alm Sel
0: Disabled
1: Enabled

0: Disabled
1: Enabled. An alarm is triggered at output currents above
150% of regenerative unit rated current.

Default: 0
Min.: 0
Max.: 1

L8-65

(66FH)

Power Supply Fault
Detection Selection

Vpn Ripple Sel
0: Disabled
1: Coast to Stop
2: Alarm Only

There is normally no need to change this parameter from
the default value.
Monitors the ripple of DC BUS voltage and detects Input
Power Supply Fault(PF2) when the ripple is too bad.
0: No detection
1: Stop operation (fault)
2: Continue operation (minor fault)

Default: 0
Min.: 0
Max.: 2

No.

(Address

Hex)

Name

LCD Display

Description

Values

TOEP_C710656_08B_1_0.book 165 ページ 2015年2月5日 木曜日 午前10時7分

Advertising