2.2 Mechanical Installation

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

25

Mec

h

an

ic

al

In

st

al

la

tio

n

2

2.2 Mechanical Installation

This section outlines specifications, procedures, and the environment for proper mechanical installation of the
regenerative unit.

Installation Environment

Install the regenerative unit in an environment matching the specifications in

Table 2.1

to help prolong the optimum

performance life of the regenerative unit.

Table 2.1 Installation Environment

WARNING! Fire Hazard. When installing an IP00/IP20 regenerative unit in a closed panel or cabinet, sufficiently cool the panel or

cabinet with a cooling fan or air conditioner so that the air temperature entering the regenerative unit is 50

°

C (122

°

F) or cooler. Failure

to comply could result in overheating and fire.
NOTICE: Avoid placing regenerative unit peripheral devices, transformers, or other electronics near the regenerative unit as the noise

created can lead to erroneous operation. If such devices must be used in close proximity to the regenerative unit, take proper steps to

shield the regenerative unit from noise.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the regenerative unit during installation.

Failure to comply could result in damage to the regenerative unit. Place a temporary cover over the top of the regenerative unit during

installation. Remove the temporary cover before regenerative unit start-up, as the cover will reduce ventilation and cause the

regenerative unit to overheat.

Installation Orientation and Spacing

Install the regenerative unit upright as illustrated in

Figure 2.1

to maintain proper cooling.

Figure 2.1

Figure 2.1 Correct Installation Orientation

Environment

Conditions

Installation Area

Indoors

Ambient

Temperature

IP00/Open Type enclosure: -10

°C to +50°C (14°F to 122°F)

IP20/NEMA Type 1 enclosure: -10

°C to +40°C (14°F to 104°F)

Regenerative unit reliability improves in environments without wide temperature fluctuations.
When using the regenerative unit in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that
the air temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the regenerative unit.

Humidity

95% RH or less and free of condensation

Storage

Temperature

-20

°C to +60°C (-4°F to +140°F)

Surrounding Area

Install the regenerative unit in an area free from:

• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.

Altitude

1000 m (3281 ft) or lower, up to 3000 m (9843 ft) with derating. Refer to

Derating Data on page 151

for details.

Vibration

10 to 20 Hz at 9.8 m/s

2

, 20 to 55 Hz at 5.9 m/s

2

(2A03P5 to 2A0053, 4A03P5 to 4A0073)

10 to 20 Hz at 9.8 m/s

2

, 20 to 55 Hz at 2.0 m/s

2

(2A0073 to 2A0105, 4A0105 to 4A0300)

Orientation

Install the regenerative unit vertically to maintain maximum cooling effects.