B.2 Parameter Tables

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

157

Par

ame

te

r Li

st

B

C: Tuning

Tuning parameters set the voltage increase time, voltage decrease time, carrier frequency, and DC bus voltage control.

F: Options

F parameters program the regenerative unit for communication options and to function with option cards.

No.

(Address

Hex)

Name

LCD Display

Description

Values

C7: DC Bus Voltage Control

C7-14

(759H)

Bias Voltage at
Operation Start

Vd Bias@Start

Normally, it is not necessary to change the setting of this
parameter. Adjusts the level to start regenerative operation
for automatic operation. Operation starts when the Voltage
Deviation (U1-73) exceeds the sum of C7-14 and C7-15.
Operation stops when Voltage Deviation goes below the
set value of C7-14.

200 V Class
Default: 2.0
Min.: 00.0
Max.: 50.0
400 V Class
Default: 4.0
Min.: 0.0
Max.: 100.0

C7-15

(75AH)

Voltage Hysteresis
Width at Operation
Start/Stop

Vd Hysteresis

Normally, it is not necessary to change the setting of this
parameter. Adjusts the level to start regenerative operation
for automatic operation. Operation starts when the Voltage
Deviation (U1-73) exceeds the sum of C7-14 and C7-15.
Operation stops when Voltage Deviation goes below the
set value of C7-14.

200 V Class
Default: 3.0
Min.: 00.0
Max.: 50.0
400 V Class
Default: 6.0
Min.: 0.0
Max.: 100.0

C7-16

(75BH)

Minimum Operation
Time

Minimum On Time

Sets the minimum operation time from the start of
operation to when operation stops in automatic operation.

Default: 1.00 s
Min.: 0.00 s
Max.: 600.00 s

C7-43

(112AH)

Input Voltage Offset
Adjustment

Vac Bias Adj Sel

There is normally no need to change this parameter from
the default value. This parameter is for factory setting.
If the setting is not correct, the regenerative unit may be
damaged.
0: Standard
1: Start offset adjustment. (The parameter returns to 0 after
it is set.)
2: Offset adjustment not required. (The parameter returns
to 0 after it is set.)

Default: 0
Range: 0 to 2

C7-50

(113BH)

Operation Ready
ON Delay Time

Conv READY delay

Sets the delay time to turn on the Operation Ready signal
(H2-†† = 6).

Default: 0 ms
Min.: 0 ms
Max.: 500 ms

C7-53

(111FH)

Automatic
Operation Stop
Power

Autorun Power

Sets the power to stop the automatic operation. When in
automatic operation, Regenerative unit stops automatic
operation when the power becomes lower than
regenerative load.

Default: 50%
Min.: 0%
Max.: 100%

No.

(Address

Hex)

Name

LCD Display

Description

Values

F4: Analog Monitor Card (AO-A3)

F4-01

(391H)

Terminal V1
Monitor Selection

AO Ch1 Select

Sets the monitor signal for output from terminal V1. Set
this parameter to the last three digits of the desired
U†-†† monitor. Some U parameters are available only
in certain control modes.

Default: 0
Min.: 000
Max.: 408