Changing parameter settings or values, 3 the drive and programming modes – Yaskawa R1000 Series Power Regenerative Unit User Manual

Page 73

Advertising
background image

4.3 The Drive and Programming Modes

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

73

S

ta

rt

-Up Pr

ogr

amming

&

O

p

er

at

io

n

4

Changing Parameter Settings or Values

This example explains changing b1-02 (Run Command Selection) from 01 to 00.

Step

Display/Result

1.

Turn on the power to the regenerative unit. The initial display appears.

2.

Press the

or

key until the Parameter Setting Mode screen appears.

3.

Press the

key to enter the parameter menu tree.

4.

Press

or

key to select the B parameter group.

5.

Press

two times.

6.

Press

to view the current setting value (1). “1” Flashes.

7.

Press the

key and enter 0.

8.

Press

and the regenerative unit will confirm the change.

9.

The display automatically returns to the screen shown in Step 4.

10. Press the

key until back at the initial display.

- MODE -

U1-55= 0A

U1-57= 0kW
U1-58=0.0Hz

DRV

AC Current

Rdy

RSEQ
RREF

- MODE -

PRG

Programming

-PRMSET-

Initialization

Select Language

PRG

A

1-00=

0

-PRMSET-

Sequence

Run Source 1

PRG

b1-02=1

-PRMSET-

Sequence

Run Source 1

PRG

b1-02=1

-PRMSET-

b1-02=1 *1*
Digital Inputs

PRG

Run Source 1

-PRMSET-

b1-02=1 *1*
Digital Inputs

“1”

PRG

Run Source 1

-PRMSET-

b1-02=1 *1*
Digital Inputs

“1”

PRG

Run Source 1

Entry Accepted

-PRMSET-

b1-02=0 *0*

Operator

PRG

Run Source 1

- MODE -

U1-51= 330V

U1-52= 330V
U1-03= 0.00A

DRV

Volt Ref(OPR)

Rdy

RSEQ
LREF

TOEP_C710656_08B_1_0.book 73 ページ 2015年2月5日 木曜日 午前10時7分