YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
73
S
ta
rt
-Up Pr
ogr
amming
&
O
p
er
at
io
n
4
◆ Changing Parameter Settings or Values
This example explains changing b1-02 (Run Command Selection) from 01 to 00.
Step
Display/Result
1.
Turn on the power to the regenerative unit. The initial display appears.
2.
Press the
or
key until the Parameter Setting Mode screen appears.
3.
Press the
key to enter the parameter menu tree.
4.
Press
or
key to select the B parameter group.
5.
Press
two times.
6.
Press
to view the current setting value (1). “1” Flashes.
7.
Press the
key and enter 0.
8.
Press
and the regenerative unit will confirm the change.
9.
The display automatically returns to the screen shown in Step 4.
10. Press the
key until back at the initial display.
- MODE -
U1-55= 0A
U1-57= 0kW
U1-58=0.0Hz
DRV
AC Current
Rdy
RSEQ
RREF
- MODE -
PRG
Programming
←
→
-PRMSET-
Initialization
Select Language
PRG
A
1-00=
0
←
→
-PRMSET-
Sequence
Run Source 1
PRG
b1-02=1
←
→
-PRMSET-
Sequence
Run Source 1
PRG
b1-02=1
-PRMSET-
b1-02=1 *1*
Digital Inputs
PRG
Run Source 1
←
→
-PRMSET-
b1-02=1 *1*
Digital Inputs
“1”
PRG
Run Source 1
←
→
-PRMSET-
b1-02=1 *1*
Digital Inputs
“1”
PRG
Run Source 1
←
→
Entry Accepted
←
→
-PRMSET-
b1-02=0 *0*
Operator
PRG
Run Source 1
- MODE -
U1-51= 330V
U1-52= 330V
U1-03= 0.00A
DRV
Volt Ref(OPR)
Rdy
RSEQ
LREF