6.2 Inspection
118
YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
Cooling System Periodic Inspection
Cooling Fan,
Circulation Fan,
Control Board
Cooling Fan
• Check for abnormal oscillation or unusual noise.
• Check for damaged or missing fan blades.
• Replace as required.
•
for information on cleaning
or replacing the fan.
Heatsink
Inspect for dust or other foreign material collected on
the surface.
Use a vacuum cleaner to remove dust and dirt, but do not
allow it to come into contact with product components.
Display Periodic Inspection
Digital Operator
• Make sure data appears on the display properly.
• Inspect for dust or other foreign material that may
have collected on surrounding components.
• Contact the nearest sales office if there is any trouble
with the display or keypad.
• Clean the digital operator.
Inspection Area
Inspection Points
Corrective Action
Checked