A.2 regenerative unit specifications – Yaskawa R1000 Series Power Regenerative Unit User Manual

Page 149

Advertising
background image

A.2 Regenerative Unit Specifications

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

149

S

p

ec

ifi

ca

tio

n

s

A

A.2 Regenerative Unit Specifications

Item

Specification

Input

Rated Voltage

Rated Frequency

200 V Class: 200 to 240 Vac 50/60 Hz
400 V Class: 380 to 480 Vac 50/60 Hz

Allowable Voltage

Fluctuation

-15 to +10%

Allowable Frequency

Fluctuation

±2%

Control

Characteristics

Control Method

120

° excitation method

Input Power Factor

0.9 minimum (for rated load)

Regenerative Torque

150% 30 s, 100% 25% ED 60 s, 80% continuous

Voltage Reference Range

200 V Class: 300 to 360 Vdc
400 V Class: 600 to 730 Vdc

Main Control Functions

Cooling fan on/off switch, MEMOBUS/Modbus Communication (RS-422/RS-485 maximum,
115.2 kbps)

Protection

Functions

Momentary Overcurrent

Protection

Operation stops when unit current is approximately 250% of the rated power supply current.

Open Fuse

Operation stops if the fuse opens.

Overload

Operation stops when unit current is 150% of the rated power supply current for 30 s.

Overvoltage Protection

(Output)

200 V class: Stops when DC bus voltage exceeds approximately 410 Vdc
400 V class: Stops when DC bus voltage exceeds approximately 820 Vdc

Overvoltage Protection

(Input)

200 V class: Stops when input voltage exceeds approximately 227 Vac
400 V class: Stops when input voltage exceeds approximately 554 Vac

Undervoltage Protection

(Output)

200 V class: Stops when DC bus voltage is below approximately 190 Vdc
400 V class: Stops when DC bus voltage is below approximately 380 Vdc

Undervoltage Protection

(Input)

200 V class: Stops when input voltage is below approximately 150 Vac
400 V class: Stops when input voltage is below approximately 300 Vac

Momentary Power Loss

Ride-Thru

Immediate stop after Momentary Power Loss is detected.

Power Supply Frequency

Fault

Operation stops if the input frequency deviates by

±6 Hz of rated frequency.

Heatsink Overheat

Protection

Thermistor protection

DC Bus Charge LED

Remains lit until DC bus voltage is below 50 V

Environment

Area of Use

Indoors

Ambient Temperature

IP00/Open Type enclosure: -10

°C to +50°C (14°F to 122°F)

IP20/NEMA Type 1 enclosure: -10

°C to +40°C (14°F to 104°F)

Humidity

95 RH% or less (no condensation)

Vibration/Shock

2A03P5 to 2A0053, 4A03P5 to 4A0073
10 to 20 Hz at 9.8 m/s

2

20 to 55 Hz at 5.9 m/s

2

2A0073 to 2A0105, 4A0105 to 4A0300
10 to 20 Hz at 9.8 m/s

2

20 to 55 Hz at 2.0 m/s

2

Storage Temperature

-20

°C to +60°C (-4°F to +140°F)

Altitude

1000 m (3281 ft) or lower, up to 3000 m (9843 ft) with derating.

Protection Design

IP00/Open Type enclosure, IP20/NEMA Type 1 enclosure

Standard

• UL508C
• IEC/EN 61800-5-1
• IEC/EN 61800-3

TOEP_C710656_08B_1_0.book 149 ページ 2015年2月5日 木曜日 午前10時7分