B.2 Parameter Tables

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

163

Par

ame

te

r Li

st

B

No.

(Address

Hex)

Name

LCD Display

Description

Values

H4: Analog Outputs

H4-01

(41DH)

Terminal FM
Monitor Selection

Term FM FuncSel

Selects the data to be output through terminal FM.
Set the desired monitor parameter to the digits available in
U†-††.
For example, enter “154” for U1-54.

Default: 157
Min.: 000
Max.: 408

H4-02

(41EH)

Terminal FM
Monitor Gain

Terminal FM Gain

Sets the signal level at terminal FM that is equal to 100% of the
selected monitor value.

Default: 100.0%
Min.: -999.9%
Max.: 999.9%

H4-03

(41FH)

Terminal FM
Monitor Bias

Terminal FM Bias

Sets the signal level at terminal FM that is equal to 0% of the
selected monitor value.

Default: 0.0%
Min.: -999.9%
Max.: 999.9%

H4-04

(420H)

Terminal AM
Monitor Selection

Terminal AM Sel

Selects the data to be output through terminal AM.
Set the desired monitor parameter to the digits available in
U†-††.
For example, enter “154” for U1-54.

Default: 155
Min.: 000
Max.: 408

H4-05

(421H)

Terminal AM
Monitor Gain

Terminal AM Gain

Sets the signal level at terminal AM that is equal to 100% of the
selected monitor value.

Default: 50.0%
Min.: -999.9%
Max.: 999.9%

H4-06

(422H)

Terminal AM
Monitor Bias

Terminal AM Bias

Sets the signal level at terminal AM that is equal to 0% of the
selected monitor value.

Default: 0.0%
Min.: -999.9%
Max.: 999.9%

H4-07

(423H)

Terminal FM Signal
Level Selection

Level Select1
0: 0-10 VDC
1: -10 +10 VDC
2: 4-20 mA

Sets the signal level at terminal FM.
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA

Default: 0
Min.: 0
Max.: 1

H4-08

(424H)

Terminal AM Signal
Level Selection

AO Level Select2
0: 0-10 VDC
1: -10 +10 VDC
2: 4-20 mA

Sets the signal level at terminal AM.
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA

Default: 0
Min.: 0
Max.: 1

H5: MEMOBUS/Modbus Serial Communication

Note: Restart the drive to enable MEMOBUS/Modbus communication settings.

H5-01

(0425)

Drive Slave Address Serial Comm Adr

Selects drive station node number (address) for MEMOBUS/
Modbus terminals R+, R-, S+, S-. Cycle power for the setting
to take effect.

Default: 1F (Hex)
Min.: 0
Max.: FF

H5-02

(0426)

Communication
Speed Selection

Serial Baud Rate
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19.2 kbps
5: 38.4 kbps
6: 57.6 kbps
7: 76.8 kbps
8: 115.2 kbps

0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Cycle power for the setting to take effect.

Default: 3
Range: 0 to 8

H5-03

(0427)

Communication
Parity Selection

Serial Com Sel
0: No Parity
1: Even Parity
2: Odd Parity

0: No parity
1: Even parity
2: Odd parity
Cycle power for the setting to take effect.

Default: 0
Range: 0 to 2

H5-04

(0428)

Stopping Method
after
Communication
Error

Serial Fault Sel
0: Ramp to Stop
1: Coast to Stop
3: Alarm Only

0: Ramp to stop
1: Coast to stop
3: Alarm only

Default: 3
Range: 1, 3