3.9 Control Circuit Wiring

62

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

Connect control wires as shown in

Figure 3.25

and

Figure 3.26

.

Figure 3.22

Figure 3.25 Terminal Board Wiring Guide

Figure 3.23

Figure 3.26 Terminal Board Location Inside the Regenerative Unit

For the control circuit wires, use shielded twisted-pair wires that have been prepared as shown in

Figure 3.27

.

Figure 3.24

Figure 3.27 Preparing the Ends of Shielded Cables

NOTICE: The analog signal wiring between the regenerative unit and the operator station or peripheral equipment should not exceed

50 meters when using an analog signal from a remote source. Failure to comply could result in poor system performance.

A – Loosen screw to insert wire.

C – Avoid fraying wire strands when

stripping insulation from wire.
Strip length 5.5 mm.

B – Single wire or stranded wire

D – Blade depth of 0.4 mm or less
E – Blade width of 2.5 mm or less

A – Regenerative unit side

D – Shield sheath (insulate with tape)

B – Insulation

E – Shield

C – Control device side

A

B

C

D

Preparing wire
terminal ends

YAI

YAI

A

E

B

C

D