Yaskawa R1000 Series Power Regenerative Unit User Manual

Page 195

Advertising
background image

C.9 MEMOBUS/Modbus Data Table

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

195

MEMO

BUS/Mod

bus

Co

mmunica

tion

s

C

00D2H

bit 0

ASIC Start-up Error (CPF32)

bit 1

Watch-dog Error (CPF33)

bit 2

ASIC Power/Clock Error (CPF34)

bit 3

External A/D Unit Error (CPF35)

bit 4 - 7

Reserved

bit 8

Control Circuit Error (CPF40)

bit 9

Control Circuit Error (CPF41)

bit A

Control Circuit Error (CPF42)

bit B

Control Circuit Error (CPF43)

bit C

Control Circuit Error (CPF44)

bit D

Control Circuit Error (CPF45)

bit E, F

Reserved

00D3H - 00D7H

Reserved

00D8H

oFA0† Contents (CN5-A)
bit 0

Option Compatibility Error (oFA00)

bit 1

Option not properly connected (oFA01)

bit 2

Same type of option card already connected (oFA02)

bit 3, 4

Reserved

bit 5

A/D Conversion Error (oFA05)

bit 6

Option Response Error (oFA06)

bit 7 - F

Reserved

00D9H

oFA1† Contents (CN5-A)
bit 0

Option RAM Fault (oFA10)

bit 1

Option Operation Mode Fault (SLMOD) (oFA11)

bit 2

Unit Receive CRC Error (oFA12)

bit 3

Unit Receive Frame Error (oFA13)

bit 4

Unit Receive Abort Error (oFA14)

bit 5

Option Receive CRC Error (oFA15)

bit 6

Option Receive Frame Error (oFA16)

bit 7

Option Receive Abort Error (oFA17)

bit 8 - F

Reserved

00DAH - 00DBH

Reserved

00DBH

oFA3† Contents (CN5-A)
bit 0

Communication ID Error (oFA30)

bit 1

Model Code Error (oFA31)

bit 2

Sumcheck Error (oFA32)

bit 3

Communication option timeout waiting for response (oFA33)

bit 4

MEMOBUS/Modbus Timeout (oFA34)

bit 5

Unit timeout waiting for response (oFA35)

bit 6

CI Check Error (oFA36)

bit 7

Unit timeout waiting for response (oFA37)

bit 8

Control Command Selection Error (oFA38)

bit 9

Unit timeout waiting for response (oFA39)

bit A

Control Response Selection 1 Error (oFA40)

bit B

Unit timeout waiting for response (oFA41)

bit C

Control Response Selection 2 Error (oFA42)

bit D

Control Response Selection Error (oFA43)

bit E, F

Reserved

00DCH - 00FBH

Reserved

<1> Communication error contents are saved until the fault is reset.

Register No.

Contents

TOEP_C710656_08B_1_0.book 195 ページ 2015年2月5日 木曜日 午前10時7分