C.4 MEMOBUS/Modbus Setup Parameters

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

179

MEMO

BUS/Mod

bus

Co

mmunica

tion

s

C

C.4 MEMOBUS/Modbus Setup Parameters

MEMOBUS/Modbus Serial Communication

This section describes parameters necessary to set up MEMOBUS/Modbus communications.

H5-01: Drive Slave Address

Sets the regenerative unit slave address used for communications.

Note: Cycle the power after changing this parameter to enable the new setting.

Each slave regenerative unit must be assigned a unique slave address for serial communications to work. Setting H5-01 to
any value besides 0 assigns the regenerative unit its address in the network. Slave addresses do not need to be assigned in
sequential order, but no two regenerative units may share the same address.

H5-02: Communication Speed Selection

Sets the MEMOBUS/Modbus communications speed.

Note: Cycle the power after changing this parameter to enable the new setting.

Setting 0: 1200 bps
Setting 1: 2400 bps
Setting 2: 4800 bps
Setting 3: 9600 bps
Setting 4: 19200 bps
Setting 5: 38400 bps
Setting 6: 57600 bps
Setting 7: 76800 bps
Setting 8: 115200 bps

H5-03: Communication Parity Selection

Sets the parity used for communications.

Note: Cycle the power after changing this parameter to enable the new setting.

Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity

No.

Name

Setting Range

Default

H5-01

<1> If the address is set to 0, no response will be provided during communications.

Drive Slave Address

0 to FFH

<1>

1FH

No.

Name

Setting Range

Default

H5-02

Communication Speed Selection

0 to 8

3

No.

Name

Setting Range

Default

H5-03

Communication Parity Selection

0 to 2

0