Cooling fan replacement, R1000 – Yaskawa R1000 Series Power Regenerative Unit User Manual

Page 123

Advertising
background image

6.4 Cooling Fans

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

123

Per

iodic Ins

pec

tion

&

Maint

ena

nc

e

6

Cooling Fan Replacement

WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious

personal injury. Before servicing the regenerative unit, disconnect all power to the equipment. The internal capacitor remains charged

even after the power supply is turned off. After shutting off the power, wait for at least the amount of time specified on the regenerative

unit before touching any components.

CAUTION! Burn Hazard. Do not touch a hot regenerative unit heatsink. Failure to comply could result in minor or moderate injury. Shut

off the power to the regenerative unit when replacing the cooling fan. To prevent burns, wait at least 15 minutes and ensure the

heatsink has cooled down.

NOTICE: Follow cooling fan replacement instructions. Improper fan replacement could cause damage to equipment. Make sure the fan

is facing upwards when installing the replacement fan into the regenerative unit. Replace all fans when performing maintenance to help

ensure maximum useful product life.

2A03P5 to 2A0028, 4A03P5 to 4A0028

Removing the Cooling Fan Finger Guard and Cooling Fan

1.

Depress the right and left sides of the fan cover tabs and pull upward. Remove the fan cover from the top of the
regenerative unit. The following figure illustrates a regenerative unit with a single cooling fan.

Figure 6.2

Figure 6.2 Remove the Cooling Fan Finger Guard: 2A03P5 to 2A0028, 4A03P5 to 4A0028

2.

Remove the cooling fan cartridge. Disconnect the pluggable connector and remove the fan.

Figure 6.3

Figure 6.3 Remove the Cooling Fan: 2A03P5 to 2A0028, 4A03P5 to 4A0028

R1000

R1000

TOEP_C710656_08B_1_0.book 123 ページ 2015年2月5日 木曜日 午前10時7分