D.3 UL Standards

212

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

Closed-Loop Crimp Terminal Recommendations

Yaskawa recommends UL Listed or CSA Certified crimp terminals made by JST and Tokyo DIP (or equivalent) for the
insulation cap.

Table D.4

matches the wire gauges and terminal screw sizes with Yaskawa-recommended crimp terminals,

tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge and
screw size for your regenerative unit model. Place orders with a Yaskawa representative or the Yaskawa sales department.
The closed-loop crimp terminal sizes and values listed in

Table D.4

are Yaskawa recommendations. Wire gauge values

shown in

Table D.4

are the recommended values. Refer to local codes for proper selections.

Table D.4 Closed-Loop Crimp Terminal Size

4A0105

R/L1, S/L2, T/L3

2/0

2/0 to 300

M10

18.0 to 23.0

(159 to 204)

,

4/0

4/0 to 300

M10

18.0 to 23.0

(159 to 204)

r1/ 11, 1/ 21, t1/ 31

14

14 to 10

M4

1.1 to 1.2

(9.7 to 10.6)

1

1 to 300

M10

18.0 to 23.0

(159 to 204)

4A0150

R/L1, S/L2, T/L3

250

250 to 300

M12

32.0 to 40.0

(283 to 354)

,

3/0

× 2P

3/0 to 600

M12

32.0 to 40.0

(283 to 354)

r1/ 11, 1/ 21, t1/ 31

14

14 to 10

M4

1.1 to 1.2

(9.7 to 10.6)

1/0

1/0 to 300

M12

32.0 to 40.0

(283 to 354)

4A0210

R/L1, S/L2, T/L3

3/0

× 2P

3/0 to 600

M10

18.0 to 23.0

(159 to 204)

,

4/0 × 2P

4/0 to 600

M10

18.0 to 23.0

(159 to 204)

r1/ 11, 1/ 21, t1/ 31

14

14 to 10

M4

1.1 to 1.2

(9.7 to 10.6)

2/0

2/0 to 350

M10

18.0 to 23.0

(159 to 204)

4A0300

R/L1, S/L2, T/L3

250

× 2P

250 to 600

M12

32.0 to 40.0

(283 to 354)

,

400

× 2P

400 to 600

M12

32.0 to 40.0

(283 to 354)

r1/ 11, 1/ 21, t1/ 31

14

14 to 10

M4

1.1 to 1.2

(9.7 to 10.6)

4/0

4/0 to 350

M12

32.0 to 40.0

(283 to 354)

Model

Wire Gauge (AWG, kcmil)

Screw

Size

Crimp Terminal

Model Number

Tool

Insulation Cap

Model No.

Code

<1>

R/L1,S/L2,T/L3

,

Machine No.

Die Jaw

200 V Class

2A03P5

12

M4

R5.5-4

YA-4

AD-900

TP-005

100-054-029

10

R5.5-4

YA-4

AD-900

TP-005

100-054-029

8

8-4

YA-4

AD-901

TP-008

100-054-031

6

14-NK4

YA-4

AD-902

TP-014

100-054-033

2A0005

12

M4

R5.5-4

YA-4

AD-900

TP-005

100-054-029

10

R5.5-4

YA-4

AD-900

TP-005

100-054-029

8

8-4

YA-4

AD-901

TP-008

100-054-031

6

14-NK4

YA-4

AD-902

TP-014

100-054-033

Model

Terminal

Recommended

Gauge

AWG, kcmil

Applicable Gauge

AWG, kcmil

Screw Size

Tightening Torque

Nxm (lbxin.)

+

+

+

+

+

TOEP_C710656_08B_1_0.book 212 ページ 2015年2月5日 木曜日 午前10時7分