4.6 Verifying Parameter Settings and Backing Up Changes
82
YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
■
Copying Procedure for the LCD Operator
The LCD operator can perform the following operations by changing the o3-01(Copy Function Selection) parameter in
the regenerative unit.
Read (o3-01 = 1)
Copies all parameters from the regenerative unit to the LCD operator.
Note: There is a limit to the number of read operations that you can perform from the LCD operator. As a guide, do not perform more
than 100,000 read operations.
Copy (o3-01 = 2)
Copies all parameters from the LCD operator to the regenerative unit.
Verify (o3-01 = 3)
Compares the parameters in the regenerative unit with the parameter settings saved on the LCD operator for matches.