Power Coordinating Reactor/Current Suppression Reactor

To conform to UL508C, connect the power coordinating reactor to the input side of the drive, input fuses, and the current
suppression reactor to the input side of the regenerative unit. Refer to

Standard Configuration Devices on page 204

for

details.

Installing Standard Configuration Devises

NOTICE: If a fuse is open or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of the peripheral

devices. Check the wiring and the selection of peripheral devices to identify the cause. Contact Yaskawa before restarting the

regenerative unit or the peripheral devices if the cause cannot be identified.

Recommended Standard Configuration Devises

Yaskawa recommends installing standard configuration devises to maintain compliance with UL508C.
Refer to

Standard Configuration Devices on page 204

for details.

Low Voltage Wiring for Control Circuit Terminals

Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The
external power supply shall be a CSA certified or cUL Listed Class 2 power source only or equivalent.

Table D.5 Control Circuit Terminal Power Supply

Regenerative Unit Short-Circuit Rating

This regenerative unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical
amperes, 240 Vac for 200 V class regenerative units and 480 Vac for 400 V class regenerative units, when protected by
fuses as specified on the

Table D.6

.

Connect the regenerative unit to an AC drive which has built-in semiconductor short-circuit protection and conforms to
UL short-circuit test.

Model

Wire Gauge (AWG, kcmil)

Screw

Size

Crimp

Terminal

Model

Number

Tool

Insulation

Cap

Model No.

Code

r1/ 11, 1/ 21,

t1/ 31

Machine

No.

Die Jaw

2A03P5 to 2A0028,

4A03P5 to 4A0028

14

M3.5

R2-3.5

YA-4

AD-900

TP-003

100-106-516

2A0035 to 2A0105,

4A0035 to 4A0300

14

M4

R2-4

YA-4

AD-900

TP-003

100-106-517

Input / Output

Terminal Signal

Power Supply Specifications

Multi-function digital inputs

S1, S2, S3, S4, S5, S6, S7, S8,
SC

Use the internal LVLC power supply of the regenerative unit. Use class 2 for
external power supply.

Multi function analog inputs

+V, -V, A1, A2, A3, AC