5.4 Alarm Detection

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

107

Tr

ou

blesh

oot

ing

5

Digital Operator

Display

Minor Fault Name

Detail

Alarm Output

(H2-†† = 10)

oL2

Overload

The thermal sensor of the regenerative unit triggered the unit overload
protection.

YES

Cause

Possible Solutions

Load is too heavy.

Reduce the load.

The regenerative unit does not operate.

Start regenerative unit operation first, and then start regenerative unit operation.

Digital Operator

Display

Minor Fault Name

Detail

Alarm Output

(H2-†† = 10)

ov

DC Bus Overvoltage

The DC bus voltage exceeded the trip point.

• 200 V Class: Approximately 410 V
• 400 V Class: Approximately 820 V

YES

Cause

Possible Solutions

Electrical noise interference causes the
regenerative unit to operate incorrectly.

• Review possible solutions for handling noise interference.
• Review section on handling noise interference and check control circuit lines, main circuit lines

and ground wiring.

• If the magnetic contactor is identified as a source of noise, install a surge protector to the MC

coil.

Set number of fault restarts (L5-01) to a value other than 0.

There was a regenerative load while the
regenerative unit is stopped.

Operate the regenerative unit.

The power supply voltage is too high.

Lower the voltage so that it is within the power supply specifications of the regenerative unit.

There is a regenerative load while the
regenerative unit is stopped.

Operate the regenerative unit.

The wiring of the power supply voltage
detection circuits (

) and

the wiring of the main circuit terminals (R/L1,
S/L2, and T/L3) is not correct.

Check the wiring.
Correct the wiring.

Digital Operator

Display

Minor Fault Name

Detail

Alarm Output

(H2-†† = 10)

PAUv

Power Supply

Undervoltage

Pre-Alarm

The input power supply voltage became equal to or lower than the Input Power
Supply Undervoltage Detection Level.
200 V Class: Approximately 150 Vac
400 V Class: Approximately 300 Vac
The regenerative unit enters the baseblock state during pre-alarm. When the
input supply voltage is restored during the pre-alarm, the regenerative unit will
release the base block and continue to operate.

YES

Cause

Possible Solutions

The power supply voltage is low.

Increase the power supply voltage.

A phase loss occurred in the input power
supply.

Check the input power supply for phase loss or an imbalance in the interphase voltages.
Investigate and correct the cause and reset the fault.

Voltage detection failed.

Check r1/ 11, 1/ 21, t1/ 31 to see if they are wired correctly.

Digital Operator

Display

Minor Fault Name

Detail

Alarm Output

(H2-†† = 10)

PF3

Input Phase Loss

Detection

Abnormal oscillation continued in the input power supply voltage. (Detected
when L8-69 = 1.)

YES

Cause

Possible Solutions

The fluctuation in the voltage of the input
power supply is too large.

Investigate the cause and implement countermeasures.
Refer to

Diagnosing and Resetting Faults on page 112

for details.

A phase loss occurred in the input power
supply.
The interphase voltage balance is bad.

r1/ 11, 1/ 21, t1/ 31