5.3 Fault Detection

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

95

Tr

ou

blesh

oot

ing

5

Digital Operator

Display

Fault Name

Details

FUA

AC Fuse Blowout

The power supply fuse is open.

Cause

Possible Solution

The power supply fuse is open.

• A transistor inside the regenerative unit was destroyed.
• The input wiring or drive output has ground faulted or short circuited.

Contact your Yaskawa representative or the nearest Yaskawa sales office.

Digital Operator

Display

Fault Name

Details

FUd

DC Fuse Blowout

The DC regenerative unit output fuse is open.

Cause

Possible Solution

The main transistor failed.

Replace the regenerative unit.

The DC circuit fuse is open.

The drive failed.

Replace the drive.
For information on drive replacement, consult with your Yaskawa representative or the nearest
Yaskawa sales office.

Digital Operator

Display

Fault Name

Details

nSE

Node Setup Error

A terminal assigned to the node setup function closed during run.

Cause

Possible Solution

The node setup terminal closed during run.

Stop the regenerative unit when using the node setup function.

A Run command was issued while the node
setup function was active.

Digital Operator

Display

Fault Name

Details

oC

Overcurrent

Regenerative unit sensors detected an output current greater than the specified overcurrent level.

Cause

Possible Solution

A momentary power loss occurred.

Investigate and correct the cause and reset the fault.
Refer to

Diagnosing and Resetting Faults on page 112

for details.

One of the cables has shorted out or there is a
grounding problem.

• Check the motor cables.
• Remove the short circuit and reapply power to the regenerative unit.
• Check the resistance between the motor cables and the ground terminal

.

• Replace damaged cables.

The load is too heavy.

• Measure the current flowing into the regenerative unit.
• Replace the regenerative unit with a larger capacity regenerative unit if the current value

exceeds the rated current.

• Determine if there is sudden fluctuation in the current level.
• Reduce the load to avoid sudden changes in the current level or switch to a larger regenerative

unit.

Regenerative unit fails to operate properly due
to noise interference.

• Review the possible solutions provided for handling noise interference.
• Review the section on handling noise interference on page 393 and check the control circuit

lines, main circuit lines, and ground wiring.

The wiring of the power supply voltage
detection circuits (

) and

the wiring of the main circuit terminals
(R/L1, S/L2, and T/L3) is not correct.

Correct the wiring.

The voltage on the power supply side is very
low.

• Check the wiring.

Correct the wiring.

• Check the load on the power supply of peripheral devices that are connected to the same power

supply line.

Reduce the load.

r1/ 11, 1/ 21, t1/ 31