D.3 UL Standards

216

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum

allowable temperature of 75

°C 600 Vac UL-approved vinyl-sheathed insulation.

4A0150

3/0

×

2P

M12

80-L12

YF-1

YET-300-1

TD-323
TD-312

TP-080

100-051-558

4/0

×

2P

100-L12

YF-1

YET-300-1

TD-324
TD-312

TP-100

100-051-560

250

250

×

2P

150-L12

YF-1

YET-300-1

TD-325
TD-313

TP-150

100-051-562

300

300

×

2P

150-L12

YF-1

YET-300-1

TD-325
TD-313

TP-150

100-051-562

350

×

2P

200-L12

YF-1

YET-300-1

TD-327
TD-314

TP-200

100-051-564

400

200-L12

YF-1

YET-300-1

TD-327
TD-314

TP-200

100-051-564

500

325-12

YF-1

YET-300-1

TD-328
TD-315

TP-325

100-051-277

600

325-12

YF-1

YET-300-1

TD-328
TD-315

TP-325

100-051-277

4A0210

3/0

× 2P

M12

80-L12

YF-1

YET-300-1

TD-323
TD-312

TP-080

100-051-558

4/0

× 2P

100-L12

YF-1

YET-300-1

TD-324
TD-312

TP-100

100-051-560

250

× 2P

150-L12

YF-1

YET-300-1

TD-325
TD-313

TP-150

100-051-562

300

× 2P

150-L12

YF-1

YET-300-1

TD-325
TD-313

TP-150

100-051-562

350

× 2P

200-L12

YF-1

YET-300-1

TD-327
TD-314

TP-200

100-051-564

400

400

× 2P

200-L12

YF-1

YET-300-1

TD-327
TD-314

TP-200

100-051-564

500

500

× 2P

325-12

YF-1

YET-300-1

TD-328
TD-315

TP-325

100-051-277

600

600

× 2P

325-12

YF-1

YET-300-1

TD-328
TD-315

TP-325

100-051-277

4A0300

250

× 2P

M12

150-L12

YF-1

YET-300-1

TD-325
TD-313

TP-150

100-051-562

300

× 2P

150-L12

YF-1

YET-300-1

TD-325
TD-313

TP-150

100-051-562

350

× 2P

200-L12

YF-1

YET-300-1

TD-327
TD-314

TP-200

100-051-564

400

× 2P

200-L12

YF-1

YET-300-1

TD-327
TD-314

TP-200

100-051-564

500

× 2P

325-12

YF-1

YET-300-1

TD-328
TD-315

TP-325

100-051-277

600

× 2P

325-12

YF-1

YET-300-1

TD-328
TD-315

TP-325

100-051-277

<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.

Example 1: Model 4A0105 with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the

user should order two sets of [100-051-272].

Example 2: Model 4A0210 with 300 kcmil

× 2P for both input and output require two sets for input terminals and two sets for output terminals,

so the user should order four sets of [100-051-562].

Model

Wire Gauge (AWG, kcmil)

Screw

Size

Crimp Terminal

Model Number

Tool

Insulation Cap

Model No.

Code

<1>

R/L1,S/L2,T/L3

,

Machine No.

Die Jaw

+

TOEP_C710656_08B_1_0.book 216 ページ 2015年2月5日 木曜日 午前10時7分