4.5 Operation with the Drive Connected

78

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

Figure 4.3

Figure 4.4 Automatic Operation Command Time Chart

Forced Operation Command

When the multi-function input terminal S1 (H1-01 = 3C (default setting)) is “closed”, the regenerative unit starts
operation. When the terminal S1 is “open”, the regenerative unit stops operation after the minimum operation time has
passed.

Note: When forced operation command is selected, use a sequence so that the operation commands of the regenerative unit and the

drive are input at the same time.

Figure 4.4

Figure 4.5 Forced Operation Command Time Chart

Interlocks

Stopping the Regenerative Unit for Faults in Peripheral Devices

If an external device fails or a fault occurs, the fault contact output on the regenerative unit is activated to stop operation.
To use an external fault, set H1-…… (terminal S1 to S8 function selection) to one of the values from

Table 4.5

.

When an external fault is input, EF† is displayed on the digital operator.
The † in EF† is the number of the terminal where the external fault signal was input.

Example: If an external fault signal is input to the S3 terminal, EF3 is displayed.

Select the number to set for H1-…… according to the combination of the following three conditions:

• Use an input contact for a signal from the peripheral device.
• Use detection of an external fault.
• Stop operation (as the operation selection when an external fault is detected).

On

Run

Drive Status

Regeneration

DC Bus Voltage

AC Power Supply Voltage

×

1.35

Automatic Operation Command

Run

Regenerative

Unit Status

Current at Power

Supply Side

Operation Start Level
Operation Stop Level

Stop

Minimum Operation
Time

(C7-16)

Regeneration

On

Run

Drive Status

DC Bus Voltage

AC Power Supply Voltage

×

1.35

Forced Operation Command

Run

Regenerative

Unit Status

Current at Power

Supply Side

Minimum Operation
Time

(C7-16)