4.6 Verifying Parameter Settings and Backing Up Changes

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

81

S

ta

rt

-Up Pr

ogr

amming

&

O

p

er

at

io

n

4

Password Settings: A1-04, A1-05

The user can set a password in parameter A1-05 to restrict access to the regenerative unit. The password must be entered
to A1-04 to unlock parameter access (i.e., parameter setting A1-04 must match the value programmed into A1-05). The
following parameters cannot be viewed or edited until the value entered to A1-04 correctly matches the value set to
A1-05: A1-01, A1-03, and A2-01 through A2-33.

Note: Parameter A1-05 is hidden from view. To display A1-05, access parameter A1-04 and press

and

simultaneously.

Copy Function

Parameter settings can be copied to another regenerative unit to simplify parameter restoration or multiple regenerative
unit setup. The regenerative unit supports the following copy options:

LCD Operator (standard in all models)

The LCD operator used to operate the regenerative unit supports copying, importing, and verifying parameter settings.
Refer to

o3: Copy Function on page 167

for details.

LED Operator

The optional LED operator also supports copying, importing, and verifying parameter settings. Refer to the manual
supplied with the LED operator for instructions.

USB Copy Unit and CopyUnitManager

The copy unit is an external option connected to the regenerative unit to copy parameter settings from one regenerative
unit and save those settings to another regenerative unit. Refer to the manual supplied with the USB Copy Unit for
instructions.

Note: Connect the USB Copy Unit to the RS-422/RS-485 communication port on the regenerative unit.

CopyUnitManager is a PC software tool. It allows the user to load parameter settings from the Copy Unit onto a PC, or
from the PC onto a Copy Unit. This is useful when managing parameters for various regenerative units or applications.
Refer to the manual supplied with CopyUnitManager for instructions.

A2-01

to

A2-32

User Parameters 1 to 32

Parameters selected by the user are saved as User Parameters,
including recently viewed parameters and parameters specifically
selected for quick access.
If parameter A2-33 is set to 1, recently viewed parameters will be
listed between A2-17 and A2-32.
Parameters A2-01 through A2-16 must be manually selected by
the user.
If A2-33 is set to 0, recently viewed parameters will not be saved
to the group of User Parameters.
A2-†† parameters are now available for manual programming.

A1-00 to

o4-19

A2-33

User Parameter Automatic
Selection

0: Parameters A2-01 through A2-32 are reserved for the user to
create a group of User Parameters.
1: Save history of recently viewed parameters. Recently edited
parameters will be saved to A2-17 through A2-32 for quick
access. The most recently changed parameter is saved to A2-17.
The second most recently changed parameter is saved to A2-18,
etc.

0,1

0

No.

Parameter Name

Description

Setting

Range

Default

Setting

TOEP_C710656_08B_1_0.book 81 ページ 2015年2月5日 木曜日 午前10時7分