5.7 Diagnosing and Resetting Faults

5.7 Diagnosing and Resetting Faults

When a fault occurs and the regenerative unit stops, follow the instructions below to remove whatever conditions
triggered the fault, then restart the regenerative unit.

Fault Reset Methods

When a fault occurs, the cause of the fault must be removed and the regenerative unit must be restarted. The table below
lists the different ways to restart the regenerative unit.

Note: If the Run command is present, the regenerative unit will disregard any attempts to reset the fault. Remove the Run command

before attempting to clear a fault situation.

After the Fault Occurs

Procedure

Fix the cause of the fault, restart the
regenerative unit, and reset the fault

Press

on the digital operator when the

error code is displayed.

Resetting via Fault Reset Digital
Input S4

Close then open the fault signal digital input via
terminal S4. S4 is set for “Fault Reset” as
default (H1-04 = 14).

Turn off the main power supply if the above methods do not reset the fault. Reapply
power after the digital operator display has turned off.

LO
RE

F2

F1

ESC

RUN

STOP

ENTER

RESET

ALARM

DIGITAL OPERATOR JVOP-180

RESET

- MODE -

oC

Overcurrent

DRV

RESET

YAI

S4

Regenerative Unit

Fault Reset Switch

SN

YAI

ON

OFF