Yaskawa R1000 Series Power Regenerative Unit User Manual

Page 160

Advertising
background image

B.2 Parameter Tables

160

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

1B

Program lockout

Program Lockout

Open: Parameters cannot be edited (except for U1-01 if the reference
source is assigned to the digital operator).
Closed: Parameters can be edited and saved.

24 to 27

2C to 2F

External fault

External fault
24: NO/ Always Det,
Coast to Stop
25: NC/Always Det,
Coast to Stop
26: NO/During RUN,
Coast to Stop
27: NC/During RUN,
Coast to Stop
2C: NO/Always Det,
Alarm Only
2D: NC/Always Det,
Alarm Only
2E: NO/ During RUN,
Alarm Only
2F: NC/During RUN,
Alarm Only

24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)

3C

Forced Operation Command

Manual Run

Closed: Starts the operation of the regenerative unit.

3D

Automatic Operation
Command

Auto Run

Closed: The regenerative unit starts to operate when the voltage of the bus
increases (i.e., when a regenerative state is reached).

47

Node Setup

Node SetUp

Closed: Node setup for SI-S3 enabled.

67

Communications test mode

Comm Test Mode

Tests the MEMOBUS/Modbus RS-422/RS-485 interface. Displays
“PASS” if the test completes successfully.

No.

(Address

Hex)

Name

LCD Display

Description

Values

H2: Multi-Function Relay Outputs

H2-01

(40BH)

Terminal M1-M2
function selection
(relay)

M1-M2 Func Sel

Refer to

H2 Multi-Function Relay Output Settings on

page 160

for a description of setting values.

Note: Set unused terminals to F.

Default: 26
Min.: 0
Max.: 160

H2-02

(40CH)

Terminal M3-M4
Function Selection
(Relay)

P1/PC Func Sel

Default: 6
Min.: 0
Max.: 160

H2-03

(40DH)

Terminal M5-M6
Function Selection
(Relay)

P2/PC Func Sel

Default: 25
Min.: 0
Max.: 160

H2-06

(437H)

kWh Monitor Pulse
Output Unit Selection

Pwr Mon Unit Sel
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units

Select the output unit of the multi-function contact when
H2-01 to H2-03 is set to 3A.
1: 1 kWh
2: 10 kWh
3: 100 kWh
4: 1000 kWh

Default: 1
Min.: 1
Max.: 4

H2 Multi-Function Relay Output Settings

H2-……

Setting

Function

LCD Display

Description

0

During run

During RUN 1

Closed: A Run command is active or voltage is output.

6

Operation Ready

Drive Ready

Closed: Power up is complete and the regenerative unit is ready to accept
a Run command.

7

DC bus undervoltage

DC Bus Undervolt

Closed: DC bus voltage is below the Uv trip level set in L2-05.

H1 Multi-Function Digital Input Selections

H1-……

Setting

Function

LCD Display

Description

TOEP_C710656_08B_1_0.book 160 ページ 2015年2月5日 木曜日 午前10時7分

Advertising