Terminal functions, Power coordinating reactor, Current suppression reactor – Yaskawa R1000 Series Power Regenerative Unit User Manual

Page 142

Advertising
background image

7.4 Standard Configuration Devices Wiring

142

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

Terminal Functions

Power Coordinating Reactor

Table 7.3 Terminal Function (Power Coordinating Reactor)

Current Suppression Reactor

Table 7.4 Terminal Function (Current Suppression Reactor)

4A0105

U, V, W

50

50 to 150

2/0

2/0 to 300

50

50 to 150

M10

18.0 to 23.0

(159 to 204)

X, Y, Z

R, S, T

4A0150

U, V, W

100

100 to 150

250

250 to 300

95

95 to 240

M12

32.0 to 40.0

(283 to 354)

X, Y, Z

R, S, T

4A0210

U, V, W

80

×

2P

80 to 325

3/0

×

2P

3/0 to 600

95

×

2P

95 to 240

M12

32.0 to 40.0

(283 to 354)

X, Y, Z

R, S, T

4A0300

U, V, W

100

×

2P

100 to 325

250

×

2P

250 to 600

95

×

2P

95 to 240

M12

32.0 to 40.0

(283 to 354)

X, Y, Z

R, S, T

<1> Gauges listed here are for use in Japan.

<2> Gauges listed here are for use in the United States.

<3> Gauges listed here are for use in Europe and China.

Terminal

Function

U

Power Coordinating Reactor Inputs

These terminals are connected to the power supply.

V

W

X

Power Coordinating Reactor Outputs

These terminals are connected to the connected drive device input terminals and
input fuses.

Y

Z

Terminal

Function

X

Current Suppression Reactor Inputs

These terminals are connected to the input fuses.

Y

Z
R

Current Suppression Reactor Outputs

These terminals are connected to the regenerative unit.

S
T

Model

Terminals

For Asia

<1>

For U.S.A.

<2>

For Europe and China

<3>

Screw

Size

Tightening

Torque

Nxm

(lbxin.)

Recomm.

Gauge

mm

2

Applicable

Gauge

mm

2

Recomm.

Gauge

AWG, kcmil

Applicable

Gauge

AWG, kcmil

Recomm.

Gauge

mm

2

Applicable

Gauge

mm

2

TOEP_C710656_08B_1_0.book 142 ページ 2015年2月5日 木曜日 午前10時7分