Grounding instructions for cabinets and chassis

129

Table 20
Region-specific grounding wire requirements

Region

Grounding wire requirements

Germany

#8 AWG (10 mm

2

) green/yellow wire

Other regions in
Europe

not smaller than #6 AWG (16 mm

2

) at any point

UK

two green/yellow wires no thinner than 10 mm

2

(3/8 in.)

Grounding instructions for cabinets and chassis

Procedure 12 "Grounding the cabinets or chassis" (page 129)

describes

how to ground Small System cabinets or chassis. Repeat the steps for
each cabinet or for each chassis and chassis expander pair installed in
the system.

Procedure 12

Grounding the cabinets or chassis

Step

Action

1

Make sure that you disconnect the AC power cord from the power
outlet.

Note: For the Chassis system in an equipment rack/cabinet
configuration, equipment must be powered from the same
service panel.

DANGER

DANGER OF ELECTRIC SHOCK

Never connect power to a cabinet or chassis that is not
grounded correctly.

2

For a Cabinet system, if the cabinet is connected to a reserve power
supply unit (battery backup), make sure that the circuit breaker on
that unit is set to OFF.

DANGER

DANGER OF ELECTRIC SHOCK

Never connect backup power to a cabinet that is not
grounded correctly.

3

Install an NTBK80 grounding block near the cabinet or chassis.

Nortel Communication Server 1000

Communication Server 1000M and Meridian 1 Small System Installation and Commissioning

NN43011-310

01.04

Standard

Release 5.0

13 May 2008