66

Bracing against earthquakes

Wall studs

Maximum height of wall

4 X 16 Gauge

4.8 m (16 ft)

4 X 14 Gauge

5.1 m (17 ft)

6 X 18 Gauge

6.0 m (20 ft)

Table 19 "Maximum wall heights for stud sizes: 0.6 m (24 in.)
spacing" (page 66)

lists the maximum wall heights for different sizes

of wall studs with a 24-inch spacing

Table 19
Maximum wall heights for stud sizes: 0.6 m (24 in.) spacing

Wall studs

Maximum height of wall

Wood Studs

2 X 4 (DF #2)

3.0 m (10 ft)

2 X 6 (DF #2)

5.1 m (17 ft)

Metal Studs

2 1/2 X 20 Gauge

2.4 m (8 ft)

2 1/2 X 18 Gauge

2.7 m (9 ft)

2 1/2 X 14 Gauge

3.0 m (10 ft)

3 5/8 X 20 Gauge

3.3 m (11 ft)

3 5/8 X 18 Gauge

3.6 m (12 ft)

3 5/8 X 16 Gauge

3.9 m (13 ft)

3 5/8 X 14 Gauge

4.5 m (15 ft)

4 X 20 Gauge

3.6 m (12 ft)

4 X 18 Gauge

3.9 m (13 ft)

4 X 16 Gauge

4.2 m (14 ft)

4 X 14 Gauge

4.8 m (16 ft)

6 X 18 Gauge

5.4 m (18 ft)

3

Determine where to place the fasteners.

Refer to

Figure 21 "Plywood fastener locations for wood and metal

stud walls, 16 inch spacing" (page 68)

through

Figure 23 "Plywood

fastener locations for concrete and masonry walls" (page 70)

if you

Nortel Communication Server 1000

Communication Server 1000M and Meridian 1 Small System Installation and Commissioning

NN43011-310