Grounding instructions for cabinets and chassis

131

Figure 55
Ground/Earth lug in the NTAK11 system cabinets

5

For the Chassis system:Install a #6 AWG (#40 Metric Wire Gauge)
ground wire from the ground lug on the back of the chassis to the
NTBK80 grounding block.

Consider each chassis and chassis expander pair as one ground.
Jumper the chassis expander ground to the chassis ground. See

Figure 56 "Grounding a chassis and chassis expander pair" (page
132)

.

Place a DO NOT DISCONNECT tag on the ground wire.

Nortel Communication Server 1000

Communication Server 1000M and Meridian 1 Small System Installation and Commissioning

NN43011-310

01.04

Standard