Grounding instructions for cabinets and chassis

133

Figure 57
NTBK80 grounding block

6

Connect the grounding block to the ground bus in the AC power
service panel, using #6 AWG wire. See

Table 20 "Region-specific

grounding wire requirements" (page 129)

for region-specific

grounding requirements.

DANGER

DANGER OF ELECTRIC SHOCK

A qualified technician or electrician must make the
connection in the AC power service panel.

7

Place a DO NOT DISCONNECT tag on the ground wire at the
service panel.

8

Test the ground.

—End—