Table 21 dc power requirements, Procedure 16 installing the dc power supply – Nortel Networks 1000M User Manual

Page 142

Advertising
background image

142

Installing the power supplies for the Cabinet system

d. Reset the circuit breaker once the ground connection is verified.

—End—

DC power supply installation

Table 21
DC power requirements

Minimum

(see note)

Nominal

Maximum

Recommended

-42.5 V DC

-52 V DC

-54 V DC

Limits

-42.5 V DC

-52 V DC

-57 V DC

Noise (CMESS)

25 dBrnc

Current

12 Amps

AC Ripple

100 mv RMS

Note: The NTDK72 DC breaker will trip at -42.5 +/- 1.0 V DC.

Refer to the requirements for the DC-powered version in the chapters
on system and site requirements in Communication Server 1000M and
Meridian 1 Small System Planning and Engineering (NN43011-220)
for
detailed information about DC power requirements.

Procedure 15

Installing the DC power supply

Step

Action

1

Make sure the switches on the power supply are properly set. Refer
to

Figure 60 "NTDK70 and NTDK72 power supply switch settings"

(page 139)

of this chapter.

2

Insert the power supply into the first slot on the left of the card shelf
(refer to

Figure 59 "Power supply location, main and expansion

cabinets" (page 138)

).

WARNING

Make sure the circuit breaker on the faceplate of the
power supply is OFF before continuing.

3

Lock the power supply into place with the card tabs.

Nortel Communication Server 1000

Communication Server 1000M and Meridian 1 Small System Installation and Commissioning

NN43011-310

01.04

Standard

Release 5.0

13 May 2008

Copyright © 2008, Nortel Networks

.