4-8

IM 04L31A01-17E

Procedure

For the basic flow of operation, see “Setup Procedure Using Operation Keys” on page
ix. For the procedure of entering characters and numbers, see the user’s manual IM
04L31A01-01E

or IM 04L31A01-03E.

1.

Press the MENU key.
The setting mode (Control) display appears.

2.

Press the FUNC key for approximately 3 s.
The basic setting menu appears.

3.

Press the [#7] (Communication) soft key ([#9] (Communication) soft key on the
CX1000).
The communication function setting menu appears.

4.

Press the [#4] (Modbus master) soft key ([#7] (Modbus master (BASIC)) soft
key on the CX1000).
The Communication setting display appears.

CX1000 Communication (Modbus master (BASIC))
setting display

CX2000 Communication (Modbus master) setting display

Selecting the Read Cycle

5.

Use the arrow keys to move the cursor to the [Read cycle] box.

6.

Press one of the soft keys from [125ms] to [10s] to select the data cycle.

Selecting the Timeout Time

7.

Use the arrow keys to move the cursor to the [Timeout] box.

8.

Press one of the soft keys from [125ms] to [1min] to select the timeout.

4.3 Setting the Modbus Master Function